Universal IS Pressure Transmitter UniTrans

Operation of Transmitters with Display

Subject to change due to technical modifications.

© Copyright WIKA Alexander Wiegand GmbH & Co. KG / Germany

WIKA Alexander Wiegand GmbH & Co. KG · Alexander-Wiegand-Str. · 63911 Klingenberg · (09372) 132 - 710 · Fax - 706 · E-mail: [email protected] · www.wika.de

120

9.4

Default Data (factory settings)

Function

Defaults

Display

Unit of measurement
(Line 1)
Line 2
Line 3

Pressure display (in bar)

Temperature display (in °C)
Sensor’s nominal pressure range (in bar)

Calibration

zero 4 mA
span 20 mA

nom. pressure range start
nom. pressure range end

Output

Damping
Inversion
Fault
Limits
I-offset

0 s
no
21 mA (upscale)
3.8 ... 20.5 mA
0 mA

Service password

no active password

Service mounting correction

not activated

Language

English

Evaluation

linear
density

yes
1 g/cm

3

Calibrated special measurement ranges i. e. 4 bar on a 6 bar transmit-
ter can be adjusted by factory pre-setting. A reset to default will reset
the sensor back to its nominal range (i. e. 6 bar). The factory pre-setting
gets lost.