Universal IS Pressure Transmitter UniTrans

Operation of Devices without Displays

22

669

39

.0

5 D

/G

B

06

/2

00

6

Subject to change due to technical modifications.

© Copyright WIKA Alexander Wiegand GmbH & Co. KG / Germany

WIKA Alexander Wiegand GmbH & Co. KG · Alexander-Wiegand-Str. · 63911 Klingenberg · (09372) 132 - 710 · Fax - 706 · E-mail: [email protected] · www.wika.de

115

Example:
A pressure transmitter with 0 ... 400 mbar (nominal pressure) is to be programmed.
The liquid’s surface (with a density of 1) is 1 m above the diaphragm at the zero point.
The maximum (span end-point) should be 3 m. The measuring range (span) is 200
mbar.

This means that the output must be set to 12 mA during programming.

A change in the zero point has no effect on the adjusted span.
However, if the span end-point is higher than the peak value of the
transmitter’s nominal pressure range, then the span end-point is fixed
at this peak value and the span is reduced accordingly.
A change in the span setting has no effect on the zero point. The zero
point and span end-point must fall within the transmitter’s nominal
pressure range.

A test / correction of the zero point is suggested after adjusting the
span in order to maintain optimum accuracy.
A mounting correction should be carried out before or after making an
adjustment without pressure (dry adjustment) (see 8.4.3). The trans-
mitter must therefore be placed in the reference position for the mea-
surement (installation site) without pressure on the diaphragm.

I

calc

pressure difference (span) (300 mbar -100 mbar)

Sensors nominal pressure 400 mbar

----------------------------------------------------------------------------------------------------------------------------------

16 mA 4 mA

+

12 mA

=

=

Enter

Value

Access

Function

... to Imeas = Icalc

Activate

Keypad
(2 sec.)

Calculate

Calibration Value

Calibration of span, without display, without pressure

current value decreases

Confirm

Calibration Value

... to Imeas = Icalc

current value increases

Icalc =

(2 sec.)

(2 sec.)

027-DS-GB