WIKA IUT-11 User Manual
Page 44
Universal IS Pressure Transmitter UniTrans
Operation of Transmitters with Display
22
669
39
.0
5 D
/G
B
06
/2
00
6
Subject to change due to technical modifications.
© Copyright WIKA Alexander Wiegand GmbH & Co. KG / Germany
WIKA Alexander Wiegand GmbH & Co. KG · Alexander-Wiegand-Str. · 63911 Klingenberg · (09372) 132 - 710 · Fax - 706 · E-mail: [email protected] · www.wika.de
119
9.2
Key Functions
9.3
The Programming Mode
The transmitter can be programmed before or after installation.
The keypad is activated and the device can be programmed by simultaneously press-
ing the "esc" and "ok" keys (for 2 sec.). This method is used to access the main
menus. Each main menu has one or more sub-menus and each sub-menu, may have
its own sub-menus.
Button
Functions
Main Menu
Sub-menu
Edit Functions
back to the previous
menu option
back to the previous
menu option
increase value
forward to next menu
option
forward to next menu
option
decrease value
back to value display
without saving
back to main menu
without saving
back without saving
to the sub-menu
to the edit functions
save value
activate keypad (push simultaneously; 2 s)
The keypad becomes inactive after 10 min. of disuse. All settings will de-
fault to previously stored values. Only settings that have been confirmed
with the "OK" function are stored.
A change in the starting measurement (zero point) has no effect on the
measurement span. Likewise, a change in the span has no effect on the
starting measurement.
An error signal occurs when the zero point or span settings fall outside of
the sensor’s nominal pressure range during calibration with pressure.
Nothing is saved.