Universal IS Pressure Transmitter UniTrans
Operation of Transmitters with Display
22
669
39
.0
5 D
/G
B
06
/2
00
6
Subject to change due to technical modifications.
© Copyright WIKA Alexander Wiegand GmbH & Co. KG / Germany
WIKA Alexander Wiegand GmbH & Co. KG · Alexander-Wiegand-Str. · 63911 Klingenberg · (09372) 132 - 710 · Fax - 706 · E-mail: [email protected] · www.wika.de
127
Example:
Level 100 %:
4000 mm
Density:
1 g/cm3
Density correction:
0.9 g/cm3
Span end point:
The span (end-point) must be re-calibrated (with or without pressure) to 4000 mm in
order to prevent a 4000 mm level tank from being overfilled.
Please check the following if "Wrong Entry" appears in the Evaluation
menu:
• whether or not more than 32 value pairs are entered in the table for tank
linearization (please note: P 0 and P 31 are fixed at 0% and 100% re-
spectively)
• whether or not an existing height value was tried to be stored again
Please enter correct values.
A change or correction in the density causes a change in the span end-
point’s unit of measure (mm, m, inch, feet). The span end-point must be
re-calibrated when changing the medium to be measured (due to a
change in density).
4000 mm
1 g/cm
3
⋅
0.9 g/cm
3
----------------------------------------------------- 4444
mm
=
Important