Universal IS Pressure Transmitter UniTrans
Installation
22
669
39
.0
5 D
/G
B
06
/2
00
6
Subject to change due to technical modifications.
© Copyright WIKA Alexander Wiegand GmbH & Co. KG / Germany
WIKA Alexander Wiegand GmbH & Co. KG · Alexander-Wiegand-Str. · 63911 Klingenberg · (09372) 132 - 710 · Fax - 706 · E-mail: [email protected] · www.wika.de
111
Terminal Configuration
For transmitters with M12 x 1 circular connector, below are the wiring details:
1 Positive
3 Negative
7.5
Pressure Compensation when using a Relative Pressure Sensor
A Goretex diaphram is used to compensate for the atmospheric pressure under the
IP 65 Protection Method.
A special cable with capillaries for relative pressurization is used for
Ingress Protection IP 67.
When connecting the clamps ’L+’ and ’I’ the safety-related nominal values
(See chapter 6.7) must be observed.
Only approved intrinsically safe ammeters may be connected to the test
circuit between the clamps ’L+’ and ’I’.
The internal resistance of the multimeter must be < 100
Ω
.
The unit must be properly grounded in order to guarantee EMC resistance.
Legend
Ground
L-
Negative
L+
Positive
I
Test circuit; connect the ampere meter between terminals L+ and I
Hazardous (classified)area
Non-hazardous area
Warning