In order to operate appropriately, the controller needs a configuration

that is the definition of each one of the several parameters presented

by the controller. The user must be aware of the importance of each

parameter and for each one determine a valid condition or a valid

value.

Note: Since many parameters depend on the input type chosen,

it is recommended that the parameter TYPE be the first one to be

configured.

The parameters are grouped in levels according to their functionality

and operation easiness. The 7 levels of parameters are:

LEVEL

ACCESS

1 - Operation

Free access

2 - Tuning

Reserved access

3- R&S Programs
4- Alarms
5- Scale
6- I/Os
7- Calibration

Table 5 – Cycles of Parameters

The parameters in the operation level have easy access through the

key

P

. The access deeper levels use the combination of keys:

(BACK) and

P

(PROG) pressed simultaneously

Press

P

to advance or

to retrocede parameters within a level. At

the end of each level, the controller returns to the operation level.

Keep pressing the

P

key to move fast forward in the level.

Alternatively, the controller returns to the operation level after

pressing the

key for 3 seconds

All configuration parameters are stored in protected memory. The

values are saved when the keys

P

or

are pressed after changing

a parameter value. The value of SP is saved upon pressing the

P

key or every 25 seconds.

DESCRIPTION OF THE PARAMETERS

OPERATION CYCLE
To access the operation level parameters, press

P

until the desired

parameter is displays.

PV Indication
(Red Screen)

SP Indication

(Green Screen)

PV and SP indication – The upper display shows

the current value of PV. The lower display shows

the control SP value.

(trl

Control

Control Mode:

avto

- Means automatic control mode.

Man – Means manual control mode.

(bumpless transfer between automatic and manual

control modes).

PV Indication
(Red Screen)

MV Indication

(Green Screen)

MANIPULATED VARIABLE VALUE (MV): The

upper display shows PV value and the lower display

shows the percentage of MV applied to the control

output. When in manual control, the MV value can

be manually changed by the

and

keys. When

in auto mode the MV value can only be viewed.
To distinguish the MV display from the SP display,

the MV is shown flashing intermittently.

E pr

Enable

Program

Execution of Program - Selects the ramp and

soak profile program to be executed.

0 - does not execute program

1 to 20 number of the program to be

executed
With enabled outputs (RUN = YES), the program

starts right after the program is selected.

p.seg

Screen for indication only. When a ramp and soak

program is active, this parameter shows the number

of the segment under execution, from 1 to 9.

t.seg

Screen for indication only. When a ramp and soak

program is in execution, it shows the remaining

time to the end of the current segment, in units of

time configured in the Pr.tb parameter.

rvn

Enables control outputs and alarms.

YES

- Outputs enables.

NO

- Outputs not enabled.

CYCLE OF TUNING

Atvn

Auto-tune

Defines the control strategy to be taken:

off

– Turned off. (no PID tuning)

Fast

– Fast automatic tuning.

Full

–More accurate automatic tuning.

self

– Precise + auto - adaptative tuning

rslf

–Forces one new precise automatic

precise + auto - adaptative tuning.
T9kt

- Forces one new precise automatic + auto

- adaptative tuning when Run = YES or controller

is turned on.

pb

Proportional

Band

PROPORTIONAL BAND - Value of the term P of

the control mode PID, in percentage of the

maximum span of the input type. Adjust of

between 0 and 500.0 %. Select zero for ON/OFF

control.

ir

Integral Rate

INTEGRAL RATE - Value of the term I of the PID

algorithm, in repetitions per minute (Reset).

Adjustable between 0 and 99.99.
Displayed only if proportional band ≠ 0.

dt

Derivative Time

DERIVATIVE TIME - Value of the term D of the

control mode PID, in seconds. Adjustable between

0 and 300.0 seconds.
Displayed only if proportional band ≠ 0.

(t

Cycle Time

Pulse Width Modulation (PWM) period in seconds.

Adjustable between 0.5 and 100.0 seconds.
Displayed only if proportional band ≠ 0.

kyst

Hysteresis

CONTROL HYSTERESIS (in engineering. units):

This parameter is only shown for ON / OFF control

(Pb=0).

Adjustable between 0 and the

measurement input type span.

ACt

Action

CONTROL ACTION: For Auto Mode only.

re

Control with reverse Action. Appropriate for

heating. Turns control output on when PV

is below SP.

dir

Control with direct Action. Appropriate for

cooling. Turns control output on when PV

is above SP.

Lbd.t

Loop break

detection time.

Time interval for the LBD function. Defines the

maximum interval of time for the PV to react to a

control command. In minutes

bias

BIAS: Offset for MV (manual reset). Range: -100

% to +100 %.
Allows adding a percentage value between -100 %

and +100 %. to the MV control output
The value 0 (zero) disables the function.

ovll

Output Low

Limit

Lower limit for the control output - Minimum

percentage value assumed by the control output

when in automatic mode and in PID.
Typically configured with 0 %. Default value: 0 %