Bavd, Prty, Addr – NOVUS N1020 User Manual
Page 5: Configuration protection
N1020 Temperature Controller
NOVUS AUTOMATION
5/8
SP Low Limit
To 0-50 mV input type sets the lower range for SP and PV
indication.
Spxl
SP High Limit
Defines the SP upper limit.
To 0-50 mV input type sets the upper range for SP and PV
indication.
T1me
Timer
Time. Adjustment. 00:00 to 99:59 (HH:MM).
(same function as the one presented in the operation
level)
Tm.en
Timer Enable
Shows a copy of the T1me parameter in the operating level.
En - enables T1me parameter to the operating
level
Dis - doesn’t show the T1me parameter in the
operating level
T.str
Timer Start
Defines the mode for starting the Timer.
sP - when PV reach the temperature value in SP
rvn
- when RUN →YES
f.rst - “F” key (reset timer)
f.stp - “F” key (start/stop the timer).
T.e.(.0
Timer End Control
Off
Control behavior when the timer expires:
YES - disables the outputs (RUN = NO).
NO - outputs continue to operate.
Rate
Ramp function. Establishes the rate of increase of PV, in
degrees/minute.
Same Rate
function as showed in the operating level.
rT.en
Rate Enable
Shows a copy of the Rate
parameter in the operating
level.
En - enables the Rate parameter to the
operating level.
Dis
- doesn’t show the Rate parameter in the
operating level
rvn
Enables the control and alarm outputs.
YES
- outputs enabled.
NO
- outputs disabled.
f.key - outputs enabled/disabled function assigned
to the F key.
Same
rvn
function as showed in the operating level.
rv.en
Run Enable
Shows a copy of the
rvn
parameter in the operating level.
En - enables the
rvn
parameter in the operating
level
Dis - doesn’t show the
rvn
parameter in the
operating level
bavd
Baud Rate
Baud Rate da comunicação serial. Em kbps
1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6 e 115.2
prty
Parity
Paridade da comunicação serial.
none
Sem paridade
Ewem Paridade par
0dd
Paridade impar
Addr
Address
Endereço de Comunicação. Número que identifica
o controlador na rede de comunicação serial, entre
1 e 247.
CALIBRATION LEVEL
All of the input and output types are calibrated in the factory. If a
recalibration is required, this should be carried out by a
experienced personnel. If this cycle is accidentally accessed, pass
through all the parameters without pressing the
or
keys
pass
Password
Input of the Access Password.
This parameter is presented before the protected levels.
See item Protection of Configuration.
(alib
Calibration?
Enables or disables instrument calibration by the user,
YES: shows calibration parameters
No:
Hides the calibration parameters
inL(
Input Low
Calibration
See section MAINTENANCE / Input Calibration.
Enter the value corresponding to the low scale signal
applied to the analog input.
Only showed if
(alib
= YES
ink(
Input High
Calibration
See section MAINTENANCE / Input Calibration.
Enter the value corresponding to the full scale signal
applied to the analog input.
Only showed if
(alib
= YES
rstr
Restore
Restores the factory calibration for all inputs and outputs,
disregarding modifications carried out by the user.
ovll
Output Low Limit
Lower limit for the control output - Minimum percentage
value assumed by the control output when in automatic
mode and in PID. Typically configured with 0 %. Default
value: 0 %
ovkl
Output High Limit
Upper limit for the control output - Maximum percentage for
the control output when in automatic mode and in PID.
Typically configured with 100 %. Default value: 100 %.
(j
Cold Junction
Cold junction temperature controller.
Pas.(
Password
Change
Allows defining a new access password, always different
from zero.
Prot
Protection
Sets up the Level of Protection. See Table 05.
Freq
Frequency
Mains frequency. This parameter is important for proper
noise filtering.
snk
Shows the four first digits of the controller serial number.
snL
Shows the four last digits of the controller serial number.
CONFIGURATION PROTECTION
The controller provides means for protecting the parameters
configurations, not allowing modifications to the parameters values,
avoiding tampering or improper manipulation. The parameter
Protection (PROt), in the Calibration level, determines the
protection strategy, limiting the access to particular levels, as shown
by the Table 04.
Protection
Level
Protection Levels
1
Only the Calibration level is protected.
2
Calibration and Tuning levels.
3
Calibration, Tuning and Alarms levels
4
Calibration, Tuning, Alarms and Configuration levels
5
Calibration, Tuning, Alarms, Configuration levels
Table 04 – Levels of Protection for the Configuration
ACCESS PASSWORD
The protected levels, when accessed, request the user to provide the
Access Password for granting permission to change the
configuration of the parameters on these levels.
The prompt PASS precedes the parameters on the protected levels.
If no password is entered, the parameters of the protected levels can
only be visualized.
The Access Password is defined by the user in the parameter
Password Change (PAS.(), present in the Calibration Level. The
factory default for the password code is 1111.
PROTECTION ACCESS PASSWORD
The protection system built into the controller blocks for 10 minutes
the access to protected parameters after 5 consecutive frustrated
attempts of guessing the correct password.