N1020 Temperature Controller

NOVUS AUTOMATION

5/8

SP Low Limit

To 0-50 mV input type sets the lower range for SP and PV

indication.

Spxl

SP High Limit

Defines the SP upper limit.
To 0-50 mV input type sets the upper range for SP and PV
indication.

T1me

Timer

Time. Adjustment. 00:00 to 99:59 (HH:MM).
(same function as the one presented in the operation

level)

Tm.en

Timer Enable

Shows a copy of the T1me parameter in the operating level.

En - enables T1me parameter to the operating

level

Dis - doesn’t show the T1me parameter in the

operating level

T.str

Timer Start

Defines the mode for starting the Timer.

sP - when PV reach the temperature value in SP
rvn

- when RUN →YES

f.rst - “F” key (reset timer)
f.stp - “F” key (start/stop the timer).

T.e.(.0

Timer End Control

Off

Control behavior when the timer expires:

YES - disables the outputs (RUN = NO).
NO - outputs continue to operate.

Rate

Ramp function. Establishes the rate of increase of PV, in
degrees/minute.
Same Rate

function as showed in the operating level.

rT.en

Rate Enable

Shows a copy of the Rate

parameter in the operating

level.

En - enables the Rate parameter to the

operating level.

Dis

- doesn’t show the Rate parameter in the

operating level

rvn

Enables the control and alarm outputs.

YES

- outputs enabled.

NO

- outputs disabled.

f.key - outputs enabled/disabled function assigned

to the F key.

Same

rvn

function as showed in the operating level.

rv.en

Run Enable

Shows a copy of the

rvn

parameter in the operating level.

En - enables the

rvn

parameter in the operating

level

Dis - doesn’t show the

rvn

parameter in the

operating level

bavd

Baud Rate

Baud Rate da comunicação serial. Em kbps
1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6 e 115.2

prty

Parity

Paridade da comunicação serial.

none

Sem paridade

Ewem Paridade par

0dd

Paridade impar

Addr

Address

Endereço de Comunicação. Número que identifica
o controlador na rede de comunicação serial, entre
1 e 247.

CALIBRATION LEVEL

All of the input and output types are calibrated in the factory. If a
recalibration is required, this should be carried out by a
experienced personnel. If this cycle is accidentally accessed, pass
through all the parameters without pressing the

or

keys

pass

Password

Input of the Access Password.
This parameter is presented before the protected levels.

See item Protection of Configuration.

(alib

Calibration?

Enables or disables instrument calibration by the user,
YES: shows calibration parameters
No:

Hides the calibration parameters

inL(

Input Low

Calibration

See section MAINTENANCE / Input Calibration.
Enter the value corresponding to the low scale signal

applied to the analog input.
Only showed if

(alib

= YES

ink(

Input High

Calibration

See section MAINTENANCE / Input Calibration.
Enter the value corresponding to the full scale signal
applied to the analog input.
Only showed if

(alib

= YES

rstr

Restore

Restores the factory calibration for all inputs and outputs,
disregarding modifications carried out by the user.

ovll

Output Low Limit

Lower limit for the control output - Minimum percentage
value assumed by the control output when in automatic

mode and in PID. Typically configured with 0 %. Default
value: 0 %

ovkl

Output High Limit

Upper limit for the control output - Maximum percentage for
the control output when in automatic mode and in PID.

Typically configured with 100 %. Default value: 100 %.

(j

Cold Junction

Cold junction temperature controller.

Pas.(

Password

Change

Allows defining a new access password, always different

from zero.

Prot

Protection

Sets up the Level of Protection. See Table 05.

Freq

Frequency

Mains frequency. This parameter is important for proper

noise filtering.

snk

Shows the four first digits of the controller serial number.

snL

Shows the four last digits of the controller serial number.

CONFIGURATION PROTECTION

The controller provides means for protecting the parameters
configurations, not allowing modifications to the parameters values,
avoiding tampering or improper manipulation. The parameter
Protection (PROt), in the Calibration level, determines the

protection strategy, limiting the access to particular levels, as shown
by the Table 04.

Protection

Level

Protection Levels

1

Only the Calibration level is protected.

2

Calibration and Tuning levels.

3

Calibration, Tuning and Alarms levels

4

Calibration, Tuning, Alarms and Configuration levels

5

Calibration, Tuning, Alarms, Configuration levels

Table 04 – Levels of Protection for the Configuration

ACCESS PASSWORD
The protected levels, when accessed, request the user to provide the
Access Password for granting permission to change the
configuration of the parameters on these levels.
The prompt PASS precedes the parameters on the protected levels.

If no password is entered, the parameters of the protected levels can
only be visualized.
The Access Password is defined by the user in the parameter
Password Change (PAS.(), present in the Calibration Level. The
factory default for the password code is 1111.

PROTECTION ACCESS PASSWORD
The protection system built into the controller blocks for 10 minutes
the access to protected parameters after 5 consecutive frustrated
attempts of guessing the correct password.