N1020 Temperature Controller

NOVUS AUTOMATION

4/8

Keeping the P key pressed, at every 2 seconds the controller jumps
to the next level of parameters, showing the first parameter of each
level:

PV >> atvn >> fva1 >> type >> pass >> PV …

To enter a particular level, simply release the P key when the first
parameter in that level is displayed.
To walk through the parameters in a level, press the P key with short
strokes.
The display alternates the presentation of the parameter prompt and
its value. The parameter value is displayed with a light blinking to
differentiate it from the parameter prompt.
Depending on the level of parameter protection adopted, the
parameter PASS precedes the first parameter in the level where the
protection becomes active. See section CONFIGURATION
PROTECTION.
At the end of this manual, a table with the complete sequence of
levels and parameters is presented.

DESCRIPTION OF THE PARAMETERS

OPERATION LEVEL

PV

PV indication

Timer

Timer remaining time. Only shown when the Timer
function is in use. (

T1me

0) (HH:MM).

SP

Control SP adjustment.

T1me

Sets the Timer, 00:00 to 99:59 (HH:MM).

Rate

RATE OF PV RISE: from the current PV to the SP value.

In degrees/minute.

rvn

Enables control outputs and alarms.

YES

- Outputs enabled.

NO

- Outputs disabled.

f.key -“F” key assumes control over the RUN

command.

TUNING LEVEL

Atvn

Auto-tune

Defines the control strategy to be taken:

off

– Turned off. (no PID tuning)

Fast

– Fast automatic tuning.

Full

– More accurate automatic tuning.

self

– Precise + auto - adaptative tuning

rslf

– Forces one new precise automatic precise +

auto - adaptative tuning.

T9ht

- Forces one new precise automatic + auto -

adaptative tuning when Run = YES or

controller is turned on.

Refer to the “DETERMINING PID PARAMETERS”
section for further details on tuning strategies.

pb

Proportional

Band

PROPORTIONAL BAND -

Value of the term P of the

control mode PID, in percentage of the maximum span of
the input type. Adjust of between 0 and 500.0 %.
Select zero for ON/OFF control.

ir

Integral Rate

INTEGRAL RATE - Value of the term I of the PID

algorithm, in repetitions per minute (Reset). Adjustable
between 0 and 99.99.
Displayed only if proportional band

0.

dt

Derivative Time

DERIVATIVE TIME – Value of the term D of the control

mode PID, in seconds. Adjustable between 0 an 300.0
seconds.
Displayed only if proportional band

0.

(t

Cycle Time

Pulse Width Modulation (PWM) period in seconds.
Adjustable between 0.5 and 100.0 seconds.
Displayed only if proportional band

0.

kyst

Hysteresis

CONTROL HYSTERESIS (in engineering. units): This

parameter is only shown for ON / OFF control (Pb=0).
Adjustable between 0 and the measurement input type

span.

A(t

Action

CONTROL ACTION: For Auto Mode only.

re

Control with Reverse Action. Appropriate heating.

Turns control output on when PV is below SP.

dir

Control with Direct Action. Appropriate for

cooling. Turns control output on when PV is
above SP.

sfst

Softstart

SoftStart Function –: Time in seconds during which the
controller limits the MV value progressively from 0 to 100

%. It is enabled at power up or when the control output is
activated. If in doubt set zero (zero value disables the

Soft start function).

0ut1

0ut2

Outputs 1 and 2 function:

Off not used;
(trl control output.
A1 Alarm 1.
A2 Alarm 2.
A1a2 Alarm 1 AND Alarm 2 at the same time.

ALARMS LEVEL

Fva1

Fva2

Function Alarm

FUNCTIONS OF ALARMS. Defines the functions for the
alarms among the options of the Table 02.

Sp.a1
Sp.a2

ALARM SETPOINT: Tripping points for alarms 1 and 2.

Value that defines the point of activation for the
programmed alarms with the functions Lo or ki.
For the alarms configured with Differential type
functions, this parameter defines deviation (band).
Not used for the other alarm functions.

bla1

bla2

Blocking Alarm

BLOCK ALARM 1 and 2: This function blocks the alarms

when the controller is energized.

YES

- enables initial blocking

NO - inhibits initial blocking

When enabled, the alarm will not be active at power-up,

waiting for PV (Process Variable) to reach a non-alarm
situation. From this point on the alarm will be free to

actuate should a new alarm situation occur.

xya1

xya2

Hysteresis of Alarm

ALARM HYSTERESIS. Defines the difference between

the value of PV at which the alarm is triggered and the
value at which it is turned off.

A1t1
A2t1

Alarm Time t1

Defines the temporization time t1, for the alarms.

In seconds.

A1t2
A2t2

Alarm Time t2

Defines the temporization time t2, for the alarms.

In seconds.

CONFIGURATION LEVEL

Type

Type

INPUT TYPE: Selects the input signal type to be
connected to the process variable input. Refer to Table 1

for the available options.

fltr

Filter

DIGITAL INPUT FILTER - Used to improve the stability of
the measured signal (PV). Adjustable between 0 and 20.

In 0 (zero) it means filter turned off and 20 means
maximum filter. The higher the filter value, the slower is

the response of the measured value.

Dp.po

Decimal Point

Selects the decimal point position to be viewed in both

PV and SP.

vni t

Unit

Unit. Temperature indication in °C or °F. Not shown for

linear inputs.

0ffs

Offset

SENSOR OFFSET: Offset value to be added to the PV

reading to compensate sensor error.
Default value: zero.

Spll

Defines the SP lower limit.