Specifications, Identification, Maintenance – NOVUS N1540 Process Indicator User Manual
Page 5: Support and maintenance, Safety information, Limited warranty and limitation of liability
N1540 Indicator
NOVUS AUTOMATION
5/5
SPECIFICATIONS
DIMENSIONS: .......................................... 96 x 48 x 35 mm (1/16 DIN)
Panel Cut-out .........................................................93.0 x 45.5 mm
Approximate Weight: ............................................................ 110 g
POWER SUPPLY: ..................... 100 to 240 Vac/dc (±10 %), 50/60 Hz
Optional 24 V: .................... 12 to 24 Vdc / 24 Vac (-10 % / +20 %)
Maximum consumption: ......................................................... 6 VA
ENVIRONMENTAL CONDITIONS:
Operation Temperature: ............................................... 0 to 50 ºC
Relative Humidity: .................................................... 80 % @ 30 ºC
For temperatures above 30 ºC, reduce 3 % per ºC. Indoor use;
Installation Category II, Pollution Degree 2; altitude < 2000 m.
INPUT ................................................................ According to Table 01
Internal Resolution: ...................................... 32767 levels (15 bits)
Display Resolution: .................. 12000 levels (from -1999 to 9999)
Temperature Resolution: ........................................ 0.1 / 1 °F / °C
Input reading rate: ......................................... up to 55 per second
Precision: ... Thermocouples J, K, T, E: 0.25 % of the span ±1 ºC
................... Thermocouples N, R, S, B: 0.25 % of the span ±3 ºC
................................................................ Pt100: 0.2 % of the span
..................... 4-20 mA, 0-50 mV, 0-5 V, 0-10 V: 0.2 % of the span
Input impedance: ........ Pt100, thermocouples, 0-50 mV: > 10 M
Ω
................................................................. 0-5 V, 0-10 V: > 500 k
Ω
.............................................................................. 4-20 mA: 100
Ω
Measuring of the Pt100: ......................... 3 wire type, (α=0.00385)
With compensation of the cable length, max 50 meters,
excitation current of 0.170 mA.
OUTPUT ALARM1: .................. Relay SPST; 240 Vac / 30 Vdc / 1.5 A
OUTPUT ALARM2: .................. Relay SPST; 240 Vac / 30 Vdc / 1.5 A
24 VDC SOURCE: ................................. 24 Vdc (±10 %) / 20 mA max.
CASE: ................................................... Polycarbonate (PC) UL94 V-2
BACK PANEL: ...................................................... ABS+PC UL94 V-0
CONNECTIONS (WIRING): ........ Plug-in block terminals, 5 mm pitch
USB INTERFACE: 2.0, CDC class (virtual communications port),
MODBUS RTU protocol.
STARTS OPERATION: after 3 seconds connected to the power
supply.
CERTIFICATIONS:
IDENTIFICATION
N1540
Basic version.
N1540–24
Basic version with power supply 24 Vdc.
N1540–485
With serial communication RS485.
N1540–485–24 Version with RS485 and power 24 Vdc.
MAINTENANCE
PROBLEMS WITH THE INDICATOR
Connection errors and inadequate programming are the most
common problems encountered during the indicator operation. A final
revision can avoid loss of time and damages.
The indicator displays some messages to help the user identify the
problems.
MESSAGE
DESCRIPTION OF THE PROBLEM
----
Open input. Without sensor or signal.
Err1
Err6
Connection and/ or configuration problems. Check
the wiring and the configuration.
Other error messages may indicate hardware problems requiring
maintenance service.
CALIBRATION OF THE INPUT
All inputs are factory calibrated and recalibration should only be done
by qualified personnel. If you are not familiar with these procedures
do not attempt to calibrate this instrument.
The calibration steps are:
a) Configure the input type to be calibrated.
b) Configure the lower and upper indication limits for the maximum
span of the selected input type.
c) Connect to the input terminals a signal corresponding to a known
indication value a little above the lower display limit.
d) Access the parameter inLC. With the keys and adjust the
display reading to match the applied signal. Then press the key
to store.
e) Inject a signal that corresponds to a value a little lower than the
upper limit of indication.
f) Access the parameter inHC. With the keys and adjust the
display reading to match the applied signal. Then press the key
to store.
Note: When checking the indicator calibration with a Pt100 simulator,
pay attention to the simulator minimum excitation current
requirement, which may not be compatible with the 0.170 mA
excitation current provided by the indicator.
SUPPORT AND MAINTENANCE
This product contains no serviceable parts inside. Contact our local
distributor in case you need authorized service. For troubleshooting,
visit our FAQ
SAFETY INFORMATION
Any control system design should take into account that any part of
the system has the potential to fail. This product is not a protection or
safety device and its alarms are not intended to protect against
product failures. Independent safety devices should be always
provided if personnel or property are at risk.
Product performance and specifications may be affected by its
environment and installation. It’s user’s responsibility to assure
proper grounding, shielding, cable routing and electrical noise
filtering, in accordance with local regulations, EMC standards and
good installation practices.
LIMITED WARRANTY AND LIMITATION OF
LIABILITY
NOVUS warrants to the original purchaser that this product is free
from defects in material and workmanship under normal use and
service within one (1) year from the date of shipment from factory or
from its official sales channel to the original purchaser.
NOVUS liability under this warranty shall not in any case exceed the
cost of correcting defects in the product or of supplying replacement
product as herein provided and upon the expiration of the warranty
period all such liability shall terminate.
For complete information on warranty and liability limitations, check
appropriate section in our web sit