Protection configuration – NOVUS N1540 Process Indicator User Manual

Page 4

background image

N1540 Indicator

NOVUS AUTOMATION

4/5

bla1

bla2

Blocking

Alarm

Alarms Initial Blocking.

YES

enables the initial blocking

NO

inhibits the initial blocking

xya1

xya2

Hysteresis of

Alarm

Alarm Hysteresis. It defines the difference between the

value of PV at which the alarm is triggered and the

value at which it is turned off.

flsh

Flash

It allows signalization of an alarm conditions occurrence

by flashing the indication of PV on the indication

display.

YES

Enables alarm signalization by flashing PV.

NO

Disables the flashing PV.

INPUT CYCLE

Type

Type

Input Type. Selection of the input type, used by the

indicator. Refer to Table 01.

fltr

Filter

Digital Input Filter – Used to improve the stability of the

measured signal (PV). Adjustable between 0 and 20.

At 0 (zero) it means filter turned off and 20 means

maximum filter. The higher the filter value, the slower

is the response of the measured value.

Dp.po

Decimal Point

It determines the position of the decimal point on the

display.

vni t

Unit

It defines the temperature unit to be used:

(

Indication in Celsius.

f

Indication in Fahrenheit.

0ffs

Offset

Parameter that allows the user to make fine

adjustments to the indicated PV value.

inll

Input Low

Limit

It defines the lower value of the indication range when

the input types of 0-20 mA, 4-20 mA, 0-50 mV, 0-5 V

and 0-10 V are used.

inxl

input High

Limit

It defines the upper value of the indication range when

the input types of 0-20 mA, 4-20 mA, 0-50 mV, 0-5 V

and 0-10 V are used.

bavd

Baud Rate

Baud Rate of the serial communication. In kbps.
1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6 and 115.2

prty

Parity

Parity of the serial communication.

none

Without parity

Even

Even parity

0dd

Odd parity

Addr

Address

Communication Address. A number that identifies the

indicator in the serial communication network, between

1 and 247.

CALIBRATION CYCLE
All types of input are calibrated in the factory. In case a

recalibration is required; it shall be carried out by a specialized

professional. In case this cycle is accidentally accessed, do not

perform alteration in its parameters. The factory calibration can

be restored in the parameter rstr.

pass

Password. Entering the Access password. This

parameter is presented before the protected cycles.

See item Protection of Configuration.

(alib

Calibration. Enables the possibility for calibration of

the indicator. When the calibration is not enabled, the

related parameters are hidden.

inL(

Input Low Calibration. Indication of the low scale

calibration signal applied to the input.

ink(

Input High Calibration. Indication of the full scale

calibration signal applied to the input.

rstr

Restore. It restores the factory calibrations of the

input, disregarding any modifications carried out by the

user.

(j

Cold Junction. Temperature of the indicator cold

junction.

Pas.(

Password Change. It allows the definition of a new

access password, always different from zero.

Prot

Protection. Sets up the Level of Protection. See Table

03.

Freq

Frequency. Frequency of the local electrical network.

Sn k

First part of the indicator serial number.

Sn l

Second part of the indicator serial number.

PROTECTION CONFIGURATION

The indicator provides means for protecting the parameters

configurations, not allowing modifications to the parameters values,

avoiding tampering or improper manipulation. The parameter

Protection (PROt) in the Calibration level determines the protection

strategy, limiting the access to particular levels, as shown in the table

below.

Protection Level

Protected Levels

1

Only the Calibration level is protected.

2

Input and Calibration levels are protected.

3

Alarms, Input and Calibration levels are

protected.

Table 03 – Levels of Protection of the Configuration

ACCESS PASSWORD
The protected levels, when accessed, request the user to provide the

Access Password for granting permission to change the

configuration of the parameters on these levels.
The prompt PASS precedes the parameters on the protected levels.

If no password is entered, the parameters of the protected levels can

only be visualized.
The Access Password is defined by the user in the parameter

Password Change (PAS.(), present in the Calibration Level. The

factory default for the password code is 1111.
PROTECTION OF THE ACCESS PASSWORD
The protection system built into the indicator blocks for 10 minutes

the access to protected parameters after 5 consecutive frustrated

attempts of guessing the correct password.
MASTER PASSWORD
The Master Password is intended for allowing the user to define a

new password in the event of it being forgotten. The Master

Password doesn’t grant access to all parameters, only to the

Password Change parameter (PAS(). After defining the new

password, the protected parameters may be accessed (and

modified) using this new password.
The master password is made up by the last three digits of the serial

number of the indicator added to the number 9000.
As an example, for the equipment with serial number 07154321, the

master password is 9 3 2 1.
The indicator serial number can be obtained by pressing

for 5

seconds.