Battery Alarms.
From the
Batteries
sub-menu, type
3
to display and
configure
Battery Alarms
:
Menu Item
Description
1- Discharge
Alarm
The alarm action that occurs if battery output current exceeds the
Discharge Threshold. See
Allowed values: any standard alarm selection
a
.
2- High Voltage
Alarm
The alarm action that occurs if system battery voltage exceeds the
High Voltage Threshold. See
.
Allowed values: any standard alarm selection
a
.
3- Low Voltage
Alarm
The alarm action that occurs if system battery voltage drops below
the Low Voltage Threshold. See
Allowed values: any standard alarm selection
a
.
4- High
Temperature
Alarm
The alarm action that occurs if system battery temperature exceeds
the High Temperature Threshold. See
Allowed values: any standard alarm selection
a
.
5- Low
Temperature
Alarm
The alarm action that occurs if system battery temperature drops
below the Low Temperature Threshold. See
.
Allowed values: any standard alarm selection
a
.
6- Hardware
Current Alarm
The alarm action that occurs if the battery current is outside
reasonable limits or if a measurement fault occurs.
Allowed values: any standard alarm selection
a
.
7- Hardware
Temperature
Alarm
The alarm action that occurs if the battery temperature is outside
reasonable limits or if a measurement fault occurs.
Allowed values: any standard alarm selection
a
.
a
Standard alarm selections:
•
Major
activates the major relay.
•
Minor
activates the minor relay.
•
Relay 1
through
Relay 6
activates the relay specified.
•
Ignore
ignores the alarm.