Battery Alarms.

From the

Batteries

sub-menu, type

3

to display and

configure

Battery Alarms

:

Menu Item

Description

1- Discharge
Alarm

The alarm action that occurs if battery output current exceeds the
Discharge Threshold. See

Battery Thresholds

.

Allowed values: any standard alarm selection

a

.

2- High Voltage
Alarm

The alarm action that occurs if system battery voltage exceeds the
High Voltage Threshold. See

Battery Thresholds

.

Allowed values: any standard alarm selection

a

.

3- Low Voltage
Alarm

The alarm action that occurs if system battery voltage drops below
the Low Voltage Threshold. See

Battery Thresholds

.

Allowed values: any standard alarm selection

a

.

4- High
Temperature
Alarm

The alarm action that occurs if system battery temperature exceeds
the High Temperature Threshold. See

Battery Thresholds

.

Allowed values: any standard alarm selection

a

.

5- Low
Temperature
Alarm

The alarm action that occurs if system battery temperature drops
below the Low Temperature Threshold. See

Battery Thresholds

.

Allowed values: any standard alarm selection

a

.

6- Hardware
Current Alarm

The alarm action that occurs if the battery current is outside
reasonable limits or if a measurement fault occurs.

Allowed values: any standard alarm selection

a

.

7- Hardware
Temperature
Alarm

The alarm action that occurs if the battery temperature is outside
reasonable limits or if a measurement fault occurs.

Allowed values: any standard alarm selection

a

.

a

Standard alarm selections:

Major

activates the major relay.

Minor

activates the minor relay.

Relay 1

through

Relay 6

activates the relay specified.

Ignore

ignores the alarm.