User’s guide, Network management card – APC Network Management Card AP9617 User Manual

Page 56

background image

®

USER’S GUIDE

network management card

54

8- Current Limit
Alarm

The alarm action that occurs if one or more converters have
been forced into the “current limited” mode.

Allowed values: any standard alarm selection

a

or n of

N

b

.

9- Standby Alarm

The alarm action that occurs if one or more of the converters are
in standby mode.

Allowed values: any standard alarm selection

a

or n of N

b

.

10- Fan Failure
Alarm

The alarm action that occurs if the fan fails in one or more
converters.

Allowed values: any standard alarm selection

a

or n of N

b

.

11- Failure Alarm

The alarm action that occurs if the output of one or more
converters fails.

12- Hardware
Voltage Alarm:

The alarm action that occurs if converter voltage is outside
reasonable limits or if a voltage measurement failure occurs.

Note:

There is a single converter voltage for all converters.

Allowed values: any standard alarm selection

a

.

13- Accept Changes

Use this option to save your changes.

Converter Alarms

Description

a

Standard alarm selections:

Major

activates the major relay.

Minor

activates the minor relay.

Relay 1

through

Relay 6

activates the relay specified.

Ignore

ignores the alarm.

b

n of N

activates the alarm setting for menu item 4 (1 of N) if one converter fails, or

activates the alarm setting for menu item 5 (2 of N) if two or more converters fail.