beautypg.com

User’s guide, Network management card – APC Network Management Card AP9617 User Manual

Page 16

background image

®

USER’S GUIDE

network management card

14

Main screen status fields.

• A

Stat

field reports the Management Card status.

Stat : P+ N+ A+

• A

DC model and name

field reports the status of the DC Power Plant.

For example:

DC Power Plant : No Alarms Present

P+

The APC operating system (AOS) is functioning properly.

N+

The network is functioning properly.

N?

A BOOTP request cycle is in progress.

N–

The Management Card failed to connect to the network.

N!

Another device is using the Management Card’s IP address.

A+

The application is functioning properly.

A–

The application has a bad checksum

A?

The application is initializing

A!

The application is not compatible with the AOS.

If the AOS status is not P+, contact