Main screen status fields.
• A
Stat
field reports the Management Card status.
Stat : P+ N+ A+
• A
DC model and name
field reports the status of the DC Power Plant.
For example:
DC Power Plant : No Alarms Present
P+
The APC operating system (AOS) is functioning properly.
N+
The network is functioning properly.
N?
A BOOTP request cycle is in progress.
N–
The Management Card failed to connect to the network.
N!
Another device is using the Management Card’s IP address.
A+
The application is functioning properly.
A–
The application has a bad checksum
A?
The application is initializing
A!
The application is not compatible with the AOS.