network management card

52

Converters.

From the

Converters

sub-menu, type

1

for configurable

Converter Parameters

.

Converter Parameters

Description

1- High Voltage
Threshold (V)

If converter voltage exceeds this value, a converter high
voltage alarm occurs. To set the alarm action, see

Converter

Alarms

.

2- Low Voltage
Threshold (V)

If converter voltage drops below this value, a converter low
voltage alarm occurs. To set the alarm action, see

Converter

Alarms

.

3- Fail Safe (V)

The value sent to the converter controllers to use if
communication is lost with the master controller or if the
master controller board fails.

4- Set Point (V)

The initial set point used in the voltage control loop.

5- Fail Max (V)

The value sent to the converter controllers to define the
maximum set point allowed (the converter fail maximum
limit).

6- Fail Min (V)

The value sent to the converter controllers to define the
minimum set point allowed (the converter fail minimum
limit).

7- Communications Fail
(sec)

The time in seconds (60 by default) that a converter waits
for communication with the master controller before
resetting all its values to their defaults.

8- Accept Changes