Installation – Blodgett SBC-E Series User Manual

Page 8

background image

6

OM-SBC-E

3. Water Connection(s)

Install a check valve to prevent back flow in the incoming cold water line, as

required by local plumbing codes. Water pressure in the line should be between

30 and 60 PSI. If pressure is above 60 PSI, a pressure regulator will be needed.

These pressures must provide the 1.5 gallons per minute required for proper

steamer function.

A 3/4 inch female NH connector (garden hose type) is used to attach the water

supply to the inlet valve. Minimum inside diameter of the water feed line is 1/2

inch. Use a washer in the hose connection. Do not allow the connection to leak,

no matter how slowly. Do not over-tighten hose connections.

This equipment is to be installed to comply with the basic plumbing code of the

Building Officials and Code Administrators International, Inc. (BOCA) and the Food

Service Sanitation Manual of the Food and Drug Administration (FDA).

4. Drain Connection

Level the steamer front to back, and pitch it slightly to the front (maximum 1/4

inch) by adjusting the optional legs or the bullet feet on the optional stand.

There must be a free air gap between the end of the hose and the building drain.

The free air gap should be as close as possible to the unit drain. There must also

be no other elbows or other restrictions between the unit drain and the free air gap.

Install the drain line with a constant downward pitch.

Proper Drain Line Connection: Drain line must have a constant downward pitch of at

least 1/4” per foot. Observe local code regarding air gap spacing and drain connections.

5. Factory-Stacked Units

This section is applicable only if you are installing factory-stacked units.

Installing stacked steamers is similar to installing a single unit. The steamers are

stacked and assembled at the factory and delivered with the water connections

and drain hoses required for a single point connection.

A. Water Connection

The same water supply connection is used for both units. At the water inlet

valve a 3/4 inch female NH connector (garden hose type) is used for the

water supply.

B. Electrical Supply Connection

Separate electrical connections will be required for each steamer to be

stacked. Each steamer unit must have it’s own branch circuit protection.

C. Drain Connection

Steamers must be leveled front to back, and pitched to the rear (maximum

1/4 inch) by adjusting the bullet feet on the cabinet or stand base. For all

factory-stacked steamers, a 2-1/2 inch ID hose is attached to the unit

drain. It must be rated for boiling water.

6. Counter-Mounted Units

This section is applicable if the steamer will be mounted to a counter. All four

edges of the bottom of the steamer must be sealed with RTV to the counter if the

4 inch legs are not used. Counter must be made of a noncombustible material

such as metal or tile.

Installation

Steamer Type

NPT Pipe Size Required

3-Pan

1.5"

(2) 3-Pan

2.5"

5-Pan

1.5"

(2) 5-Pan

2.5"

10-Pan

2.0”

(2) 10-Pan

2.0"

WARNING

DO NOT CONNECT THE DRAIN DIRECTLY

TO A BUILDING DRAIN. BLOCKING THE

DRAIN IS HAZARDOUS.

CAUTION

DO NOT USE PLASTIC PIPE. DRAIN MUST BE

RATED FOR BOILING WATER.

IMPORTANT

DO NOT ALLOW WATER TRAPS IN THE LINE.

A TRAP CAN CAUSE PRESSURE BUILD-UP IN

THE CAVITY, WHICH MAY CAUSE THE DOOR

GASKET TO LEAK.

WARNING

DO NOT STACK STEAMERS WHEN

LEGS ARE USED.