Installation, Gas connection – Blodgett BLCM User Manual
Page 14
12
Installation
Gas Connection
GAs PiPinG
A properly sized gas supply system is essential for maxi-
mum oven performance. Piping should be sized to pro-
vide a supply of gas sufficient to meet the maximum de-
mand of all appliances on the line without loss of pressure
at the equipment.
Example:
NOTE: BTU values in the following example are for
natural gas.
You purchase a BLCM-61G
to add to your existing cook
line.
1. Add the BTU rating of your current appliances.
Pitco Fryer
120,000 BTU
6 Burner Range
60,000 BTU
Deck Oven
50,000 BTU
Total
230,000 BTU
2. Add the BTU rating of the new oven to the total.
Previous Total
230,000 BTU
BLCM-61G
40,900 BTU
New Total
270,900 BTU
3. Measure the distance from the gas meter to the cook
line. This is the pipe length. Let’s say the pipe length
is 40’ (12.2 m) and the pipe size is 1” (2.54 cm).
4. Use the appropriate table to determine the total ca-
pacity of your current gas piping.
The total capacity for this example is 375,00 BTU. Since
the total required gas pressure, 270,900 BTU is less than
375,000 BTU, the current gas piping will not have to be
increased.
NOTE: The BTU capacities given in the tables are for
straight pipe lengths only. Any elbows or other
fittings will decrease pipe capacities. Contact
your local gas supplier if you have any ques-
tions.
Maximum Capacity of iron Pipe in Cubic Feet of
natural Gas Per Hour
(Pressure drop of 0.5 Inch W.C.)
PiPe
LenGTH (FT)
noMinAL size, inCHes
3/4”
1”
1-1/4” 1-1/2”
2”
10
360
680
1400
2100
3950
20
250
465
950
1460
2750
30
200
375
770
1180
2200
40
170
320
660
990
1900
50
151
285
580
900
1680
60
138
260
530
810
1520
70
125
240
490
750
1400
80
118
220
460
690
1300
90
110
205
430
650
1220
100
103
195
400
620
1150
From the National Fuel Gas Code Part 10 Table 10-2
Maximum Capacity of Pipe in Thousands of
BTU/hr of Undiluted L.P. Gas at 11” W.C.
(Pressure drop of 0.5 Inch W.C.)
PiPe
LenGTH (FT)
oUTsiDe DiAMeTeR, inCHes
3/4”
1”
1-1/2”
10
608
1146
3525
20
418
788
2423
30
336
632
1946
40
287
541
1665
50
255
480
1476
60
231
435
1337
70
215
404
1241
80
198
372
1144
90
187
351
1079
100
175
330
1014
From the National Fuel Gas Code Part 10 Table 10-15