B.2.3 cr1000 datalogger example, B.2.3 – Campbell Scientific CS650 and CS655 Water Content Reflectometers User Manual
Page 51

Appendix B. SDI-12 Sensor Support
address. To exit SDI-12 transparent mode select the Close Terminal
button.
B.2.3 CR1000 Datalogger Example
1. Connect a single CS650 to the datalogger as follows:
•
Green to Control Port C1
•
Black, Orange, Clear to G
•
Red to 12V
2. In the LoggerNet Connect screen navigate to the Datalogger menu and
select Terminal Emulator. The “Terminal Emulator” window will open.
In the Select Device menu, located in the lower left-hand side of the
window, select the CR1000 station.
3. Click on the Open Terminal button.
4. Press the
CR1000>”
prompt. At the “
CR1000>” prompt, make sure the All Caps Mode box is
checked and enter the command
SDI12
3, 5, or 7” prompt, key in the control port number where the CS650 green
lead is connected and
indicates that the CS650 is ready to accept SDI-12 commands.
5. To query the CS650 for its current SDI-12 address, key in ?!
the CS650 will respond with its SDI-12 address. If no characters are typed
within 60 seconds, then the mode is exited. In that case, simply enter the
command SDI12 again, press
number when prompted.
FIGURE B-2. SDI-12 transparent mode on CR1000 datalogger using
control port 1 and changing SD1-12 address from 3 to 1
B-5