4 check that all blank modules are in place, 5 reduce the ambient temperature – APC SGI 15000 RAID User Manual

Page 136

background image

122

007-5510-002

Symptom

Cause

Action

If the ambient air is cool
(below 25 °C) and the fans
are observed to increase in
speed, then some restriction
on airflow may be causing
additional internal
temperature rise.

Note: This is not a fault
condition.

The first stage in the thermal
control process is for the fans
to automatically increase in
speed when a thermal
threshold is reached. This
may be caused by higher
ambient temperatures in the
local environment and may
be perfectly normal.

Note: This threshold
changes according to the
number of drives and PCMs
fitted.

1 Check the installation for any

airflow restrictions at either the
front or rear of the enclosure. A
minimum gap of 25mm at the front
and 50mm at the rear is
recommended.

2 Check for restrictions due to dust

build-up; clean as appropriate.

3 Check for excessive re-circulation

of heated air from rear to the front.
Use in a fully enclosed rack
installation is not recommended.

4 Check that all Blank modules are in

place.

5 Reduce the ambient temperature.