Emc-3 controller module, Inputs – High Country Tek emc-3 User Manual
Page 12
Page 12 of 39
emc-3 Controller Module
User Guide – Rev A
Inputs
Command Inputs
With only one exception, all command inputs have common settings:
1. Start Temp – The set point at which positive demand is calculated.
2. Max Temp – The set point for 100% demand.
3. Over Temp – The set point at which an error is reported due to over
temperature.
An Input demand is calculated as a percentage of error between the Start and
Max Temp set points.
The Exception to the above is when using the J1939 Percent Requested Fan
Speed (SPN 986) message, as an input at which point the demand for the input
(0% to 100%) is determined directly by the ECM.
Command Inputs are selected by entering their code number in the “Bank n
Control n” EE-Memory locations. Each Bank has 3 controls available for
assignment.
The available Command Inputs used to control the fans and their codes are as
follows;
Code
Description
1
Percent Fan Request from ECM – PGN 57344 or 57599, automatically
detected
2
Coolant Temp – PGN 65262
3
Manifold Temp – PGN 65270
4
Transmission Oil Temp – PGN 65272
5
Thermistor 1, Delphi HCT PN:206-00083 or 206-00084
6
Thermistor 2, Delphi HCT PN:206-00083 or 206-00084
7
Thermistor 3, Delphi HCT PN:206-00083 or 206-00084
NOTE:
1.
Any Input may be used in more than one bank.
2.
Individual J1939 CAN Messages are enabled / disabled by assigning them
to control an output.