Figure 3-6: 952 RS Start/Stop Pulses

INPUT (INTERROGATION PULSE)

1 MICROSECOND (RECOMMENDED)

0.2 MICROSECONDS (MINIMUM)

TIME BETWEEN PULSES IS PROPORTIONAL TO

DISTANCE BETWEEN MAGNET AND HEX HEAD

OUTPUT (START PULSE)

OUTPUT (STOP PULSE)

WITHIN 50 NANOSECONDS AFTER INTERROGATION

PULSE, START PULSE BEGINS

3.8: 952 RS (Start/Stop)

The start/stop signal interface of the BlueOx digital

output series is differential RS-422 output. The

maximum cable length for differential LDTs is 1,500

feet. To initiate a start pulse, an external device is

used. This start pulse should be a minimum of 1.0

microsecond in duration. Within 50 nanoseconds

after the leading edge of the start pulse, the LDT

will generate a start pulse of 1.0 microsecond

in duration. A stop pulse of 1.0 microsecond in

duration will follow. The time it takes from the

leading edge of the start pulse to the leading edge

of the stop pulse is proportional to the distance

between the magnet to the hex head. The order of

these two pulses is illustrated in Figure 3-6. To wire

the 952RS, see Figure 3-7. For proper grounding

information, see the beginning of this chapter.