Appendix “b” - specifications and dimensions 69, Appendix “b” - specifications and dimensions – Red Lion PCU User Manual
Page 77

APPENDIX “B” - SPECIFICATIONS AND DIMENSIONS
1. DISPLAY: Dual 4-digit
Upper Process Display: 0.4" (10.2 mm) high red LED
Lower Auxiliary Display: 0.3" (7.6 mm) high green LED
Display Messages (Model dependent):
“OLOL”
– Appears when measurement exceeds + 105% input range.
“ULUL”
– Appears when measurement exceeds - 5% input range.
“SENS”
– Appears when measurement exceeds
±“OLOL” & “ULUL” range.
“....”
– Appears when display values exceed + display range.
“-...”
– Appears when display values exceed - display range.
“SLid”
– Appears when loss of slidewire signal is detected.
“VALV”
– Appears when valve actuator error is detected.
2. POWER: Switch selectable 115/230 VAC (+10%, -15%) no observable
line variation effect, 48-62 Hz, 10 VA.
3. ANNUNCIATORS:
LED Backlight Status Indicators (Model dependent):
%PW – Lower auxiliary display shows power output in (%).
DEV – Lower auxiliary display shows deviation (error) from setpoint.
OP1 – Main control output is active.
AL1
– Alarm #1 is active.
AL2
– Alarm #2 is active (for Dual Alarm Option).
OP2 – Secondary output is active (for Secondary Output Option).
OPN – Valve positioner OPEN output is active (for Valve Positioner option).
CLS
– Valve positioner CLOSE output is active (for Valve Positioner option).
SEC – Lower auxiliary display shows second analog input (for Second
Analog Input option).
MAN – Flashing: Controller is in Manual control mode.
REM – ON: controller is in remote setpoint mode (Second Analog Input option).
– OFF: controller is in local setpoint mode (Second Analog Input option).
– Flashing: controller is in Manual control mode
(Second Analog Input optional).
-69-
Figure 39, Dimensions
DIMENSIONS In inches (mm)
Note: Recommended minimum clearance (behind the panel) for panel latch installation is 5.5" (140)H x 2.1" (53.4)W.