Red Lion PCU User Manual
Page 25

Display
Parameter
Range and
Units (Factory
Setting Value)
Description/
Comments
dt-2
Derivative
Time #2
(Secondary)
0 to 9999 sec
(0)
0 is off. This parameter does not
appear if proportional band #2 = 0.0%.
Second Analog Input models only.
SP-2
Internal
Cascade
Directed
Setpoint
-999 to 9999
(N/A)
Second Analog Input models only.
Read only parameter.
rtio
Remote
Setpoint ratio
multiplier
0.001 to 9.999
(1.000)
Second Analog Input models.
bIAS
Remote
Setpoint bias
offset
-999 to 9999
(0)
Second Analog Input models.
AL-1
Alarm 1
Value
-999 to 9999
(0)
Alarm option models only.
AL-2
Alarm 2
Value
-999 to 9999
(0)
This parameter does not appear if the
alarm option is not specified, the
secondary output option is installed,
or if locked (LOC).
CNFP
Configuration
Access Point
NO
1-IN
2-OP
3-LC
4-AL
5-02
6-SC
7-2N
8-VP
9-FS
Return to normal display mode.
Enter Configuration modules.
Configure input parameters.
Configure output parameters.
Configure parameter lockouts.
Configure alarm parameters (opt.)
Configure secondary output (opt.)
Configure serial communication
parameters (optional).
Configure second analog input
parameters (optional)
Configure valve positioner
parameters (optional)
Factory service operations (Qualified
technicians only)
End
Unit returns
to Normal
Display Mode
____
Brief display message.
-17-