REFERENCE TABLES: CONFIGURATION PARAMETER
MODULES
Configure Module 1 - Input Parameters (1-IN)
Display
Parameter
Range and Units
(Factory Setting
Value)
Description/
Comments
tYPE
Input type
VOLt - Voltage
Curr - Current
(Curr)
root
Square root
linearization
Yes/no
(no)
Second Analog Input
Models only.
dCPt
Decimal
point
0, 0.0, 0.00, or 0.000
(0.0)
If 0.000 is selected,
scaling points must
be a positive value.
rnd
Rounding
increments
1, 2, 5, 10, 50, or 100
(0.1)
Used in conjunction
with filtering to
stabilize the display
reading.
FLtr
Digital
filtering for
input signal
0 to 4
(1)
Increase number for
more filtering effect.
4 = 2/sec display
update rate.
dSP1
Scaling point
#1 Display
Value
-999 to 9999
(0.0)
Normally, key-in
display low value.
INP1
Scaling point
#1 input
signal value
key-in method
-999 to 9999
(4.00)
Normally, key-in input
low value. Press DSP
button to select signal
input method.
Signal input
method
4 to 20 mA
0-10 VDC
0.00 to 20.00
0.00 to 10.00
Normally, apply input
low value.
dSP2
Scaling point
#2 display
value
-999 to 9999
(100.0)
Normally, key-in
display high value.
Display
Parameter
Range and Units
(Factory Setting
Value)
Description/
Comments
INP2
Scaling point
#2 input
signal value
key-in method
-999 to 9999
(20.00)
Normally, key-in input
high value. Press
DSP button to select
signal input method.
Signal input
method
4 to 20 mA
0-10 VDC
0.00 to 20.00
0.00 to 10.00
Normally, apply input
high value.
SPLO
Lower limit
setpoint range
-999 to 9999
(0.0)
Set low limit below
high limit.
SPHI
Upper limit
setpoint range
-999 to 9999
(999.9)
Set high limit above
low limit.
SPrP
Setpoint ramp
rate
0.0 to 999.9
units/minute
(0.0)
0.0 is off (no ramping)
This parameter also
ramps Remote
Setpoint.
InPt
User input
PLOC - Program
disable
ILOC - Integral action
on/off
trnf - auto/manual
select
SPrP - Setpoint ramp
rate on/off
ALrS - Reset alarm
output(s)
Prnt - print request
SPSL - Remote/Local
Setpoint select
(PLOC)
Available on all
second input ( MVP
and ANA) models and
on models with
RS485.
-39-