FLOW RATE PROGRAMMING EXAMPLE
A plastics manufacturer needs to maintain a constant flow rate on a feed
stock pipeline to insure their product stays within specification. A PCU is
installed to maintain the flow by controlling a proportional control valve.
The output of the flow meter is 0 to 10 VDC. The control valve is positioned
by an electric actuator that requires a 4 to 20 mA control signal.
The following is a list of the parameter values keyed-in to the controller.
Configure Input Parameters
tYPE
VOLT
Set input signal for voltage
dCPt
0.0
Scaled display to indicate in tenths
rnd
0.1
No rounding of the display
FLtr
1
Normal input signal filtering
dSP1
0.0
Display value for scaling point 1 is 0.0
INP1
0.00
Signal value for scaling point 1 is 0.00
dSP2
100.0
Display value for scaling point 2 is 100.0
INP2
10.00
Signal value for scaling point 2 is 10.00
SPLO
0.0
Limit min. setpoint value to 0.0 units
SPHI
110.0
Limit max. setpoint value to 110.0 units
SPrP
0.1
Setpoint ramp rate = 0.1 units/minute
INPt
trnF
Allow remote switching of auto/manual mode
Configure Output Parameters
CYCt
0
Main control output and indicator off
OPAC
rEV
Main control output is reverse acting
OPLO
0
Limit min. controller power to 0%
OPHI
100
Limit max. controller power to 100%
OPFL
0
Controller output power to 0 if input overdrive
signal is detected
OPdP
2.0
Output power dampening = 2.0
CHYS
0.1
Control hysteresis set for 0.1
tcod
0
Select fastest response
ANAS
OP
Linear DC output used for control
ANLO
0.0
Control valve provides full deflection for 4 to
20 mA signal range
ANHI
100.0
Andb
2.5
Impose 2.5% deadband on Linear DC output
ANut
2
Update output once every 2 seconds
Configure Alarm Parameters
Act1
A-HI
Set alarm #1 for absolute high acting
rSt1
LAtC
Alarm set for latching
Stb1
YES
Disable alarm during power-up
AL-1
90.0
Set alarm value for 90.0
Act2
A-LO
Set alarm #2 for absolute low acting
rSt2
LAtC
Alarm set for latching
Stb2
YES
Disable alarm during power-up
AL-2
20.0
Set alarm value for 20.0
AHYS
0.1
Alarm activation hysteresis set for 0.1
-68-
}