beautypg.com

2 module 2 - s, 0 hi-t, No lo-en – Red Lion CUB5V User Manual

Page 8: No fcs, 0 lo-t, No usrin, Dsp u-asn, No hi-en, 48 code, 66 code

background image

Entering Code 66 will overwrite all user settings with

the factory settings. The meter will display

rESEt

and then

return to

CodE 00

. Press the

SEL button to exit the module.

Entering Code 50 will display the version (x.x) of the

meter. The display then returns to

CodE 00

. Press the

SEL

button to exit the module.

8

6.2 Module 2 - S

econdary

f

unction

p

araMeterS

(

2-SEC

)

SEL

Max Capture

Delay Time

Max Display

Enable

Min Display

Enable

Access Code

For Service

Operations

Min Capture

Delay TIme

Factory

Service

Operations

2-SEC

HI-En

HI-t

LO-En

LO-t

FCS

CodE

Pro

PARAMETER MENU

MIN DISPLAY ENABLE

USER INPUT ASSIGNMENT

Select the value(s) to which the User Input Function is assigned. The User

Input Assignment only applies if a selection of reset, display hold, or print and

reset is selected in the User Input Function menu.

MODE

DISPLAY

No Function

NO

DESCRIPTION

User Input disabled.

Program Mode Lock-out

P-Loc

Zero Input

(Edge triggered)

ZErO

Zero the Input Display value causing

Display Reading to be Offset.

COLOr

d-SEL

d-LEV

d-HLd

rESEt

Resets the assigned value(s) to the

current input value.

HI-LO

HI

dSP

LO

See Programming Mode Access chart

(Module 3).

YES

NO

MODE

DESCRIPTION

DISPLAY

Setpoint 1 and 2 Reset

Setpoint 1 Reset
Setpoint 2 Reset

Print and Reset

Reset both setpoint 1 and 2 outputs.

Resets setpoint 1 output.
Resets setpoint 2 output.

Same as Print Request followed by a

momentary reset of the assigned value(s).

rSt12

rSt-1

rSt-2

P-r5t

Print Request

Serial transmit of the active parameters

selected in the Print Options menu

(Module 5).

Print

2.0

HI-t

NO

LO-En

NO

FCS

MAX CAPTURE DELAY TIME

When the Input Display is above the present MAX value for the entered

delay time, the meter will capture that display value as the new MAX reading.

A delay time helps to avoid false captures of sudden short spikes.

2.0

LO-t

MIN CAPTURE DELAY TIME

When the Input Display is below the present MIN value for the entered delay

time, the meter will capture that display value as the new MIN reading. A delay

time helps to avoid false captures of sudden short spikes.

0.0

to

999.9

seconds

USER INPUT FUNCTION

NO

USrIN

dSP

U-ASN

NO

HI-En

MAX DISPLAY ENABLE

0.0

to

999.9

seconds

Select

yES

to perform either of the Factory Service Operations shown below.

FACTORY SERVICE OPERATIONS

yES

NO

YES

NO

Enables the Maximum Display Capture capability.

Enables the Minimum Display Capture capability.

The CUB5V uses stored voltage calibration values to

provide accurate voltage measurements. Over time, the

electrical characteristics of the components inside the meter

will slowly change, with the result that the stored calibration

values no longer accurately define the input circuit. For most applications,

recalibration every 1 to 2 years should be sufficient.

Calibration of the CUB5V involves an input voltage calibration, which

should only be performed by individuals experienced in calibrating electronic

equipment. Allow a 30 minute warm up before performing any calibration

related procedures. The following procedures should be performed at an

ambient temperature of 15 to 35°C (59 to 95°F).

CAUTION: The accuracy of the calibration equipment will directly affect the

accuracy of the CUB5V.

Voltage Calibration

1. Connect a precision DC voltage source with an accuracy of 0.01% or better

to the INP+ (positive) and COMM (negative) terminals of the CUB5V. Set

the output of the voltage source to zero.

2. With the display at

CodE 48

, press and hold the

SEL

button for 2 seconds. Unit

will display

CAL NO

.

3. Press the

RST

button to select the range to be calibrated.

4. Press the

SEL

button. Display reads

0.0v

.

5. With the voltage source set to zero (or a dead short applied to the input), press

SEL

. Display reads

CALC

for about 8 seconds.

6. When the display reads the selected range, apply full-scale input signal for

the range. (Note: For 200V range, apply 100V as indicated on the display.)

Press

SEL

. Display reads

CALC

for about 8 seconds.

7. Repeat steps 3 through 6 for each input range to be calibrated. When display

reads

CAL NO

, press the

SEL

button to exit calibration.

CALIBRATION

48

CodE

66

CodE

50

CodE

RESTORE FACTORY DEFAULT SETTINGS

VIEW VERSION DISPLAY

Backlight Color

(Edge Triggered)

Display Select

(Edge Triggered)
Display Intensity Level

(Edge Triggered)

Display Hold

Reset (Edge triggered)

Change backlight color with each

activation (backlight version only).

Advance once for each activation.

Increase intensity one level for each

activation (backlight version only).

Holds the assigned display, but all other

meter functions continue as long as

activated (maintained action).