PROGRAMMING EXAMPLES

SCALING A COUNTER

Example: An encoder generates 600 pulses per foot. The Desired Display is

tenths of inches. The Prescaler is determined using the formula below.

Prescaler =

1 (inch) x 10 (Decimal Point Value)



600 pulses/foot x 1 foot/ 12 inches

Where:

Desired Display = The number of Desired

Display units (revolutions,
feet, 10ths of feet, meters,
etc.).

Number of Pulses = The number of pulses

required to achieve the
Desired Display

Decimal Point Value = The desired decimal point

placement on the display.

Example: Display tenths of inches when using

Prescaler =

Desired Display Units x Decimal Point Value



Number of Pulses

= 10/50 = 0.2

Decimal
Point Value

Multiply By

0

1

0.0

10

0.00

100

0.000

1000

0.0000

10000

0.00000

100000

BACKLIGHT OPTION

Optional backlight versions of the CUB7P require an external 9 to 26 VDC

power supply. The external supply is connected between the V+ and common
terminals as shown in the drawing.

HS-6

V+-2

5-RST

1-COM

3-RST EN

LS-4

9-26 VDC

POWER SUPPLY

(Backlighting)

+

-

APPLICATION - TOTAL YARDS OF MATERIAL

A fabric manufacturer wants to know, as

economically as possible, how many whole yards of
material his lines are running. The CUB7P000 will
meet his process requirements. The encoder
measuring the material, generates a one pulse per
foot output signal. To obtain the desired display of
yards measured, a prescale value of 0.3333 is
programmed. To program the prescale value, connect
wires between RST EN (Reset Enable) and COM.
(Common); and between HS (Program Enable) and
COM. (Common) to enable the front panel push
buttons (See PROGRAMMING for more details.).
Remove these wires after programming to prevent
accidental changes to the prescale value. At the end
of each shift, the machine operator records the total
shown on the display and resets the counter to zero
via key switch.

KEY RESET

HS-6

V+-2

5-RST

1-COM

3-RST EN

LS-4

DC POWER

FOR

ENCODER

+

-

Remove these ( ) wires
after programming to prevent
accidental changes.

SIGNAL
OUTPUT

TROUBLESHOOTING

For further technical assistance, contact technical support at the appropriate company numbers listed.