14. HEATER CURRENT MONITOR INPUT (optional):
Type: 300 V max, 50 A max. Single phase, full wave monitoring of load
currents
Input: 100 mA max. input for use with external current transformers
Input Resistance: 5 Ω
Accuracy: ±3.0% full scale, 5 to 100% of range
Frequency: 50 to 400 Hz
Minimum output on time for break alarm: 350 msec
Note: To ensure isolation to SELV circuits, use a UL Listed current
transformer.
15. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: -40 to +70 °C; limited to host
Storage Temperature Range: -40 to +85 °C
Shock to IEC 68-2-27: Operational 40 g (10 g, modules w/relays)
Operating and Storage Humidity: 85% max relative humidity, non-
condensing, from 0 to +50°C
Altitude: Up to 2000 meters
16. CERTIFICATIONS AND COMPLIANCES:
CE Approved
EN 61326-1 to Industrial Locations
IEC/EN 61010-1
RoHS Compliant
UL Listed: File #E302106
17. CONSTRUCTION: Case body is all metal construction. For indoor use
only. Installation Category II, Pollution Degree 2.
18. CONNECTIONS: Removable wire clamp screw terminal blocks.
Wire Gage: 28-16 AWG terminal gage wire
Torque: 6.0 lbf-inch (96 oz-inch)
19. MOUNTING: Screws to host.
20. WEIGHT: GMP1: 8 oz (224 g)
GMP2: 8 oz (224 g)
PORT 3
ETHERNET
B
ISOLATED
A
POWER
SUPPLY
+
-
VDC
GRAPHITE HOST
GMP1 - PID MODULE
PORT 2
A
COMMUNICATIONS
A
PORT 1
PROGRAMMING
HCM
0-20mA
0-10V
RTD
TC
C
ISOLATED
POWER
SUPPLY
SSR
OUTPUTS
E
OP1-SSR1
OP2-SSR2
OP3-SSR3
ISOLATED
F
LINEAR
OUTPUT
ISOLATED
0-10V
0-20mA
INPUTS
ISOLATED
RELAY
OUTPUTS
OP1-RELAY
OP2-RELAY
OP3-RELAY
D
POWER
SUPPLY
ISOLATED
I
SSR
OUTPUTS
GMP2 - PID MODULE
OP4-SSR4
ISOLATED
0-20mA
HCM
0-10V
RTD
TC
OP1-RELAY
OUTPUTS
G
INPUTS
INPUT 1
RELAY
ISOLATED
OP2-RELAY
OP3-RELAY
OP4-RELAY
ISOLATED
0-20mA
HCM
0-10V
RTD
TC
G
INPUTS
INPUT 2
H
OP3-SSR3
OP2-SSR2
OP1-SSR1
BLOCK DIAGRAM