APPENDIX A

MODBUS REFERENCE

This appendix describes the Modbus protocol implementation of the

DPT146 transmitters.

Default Communication Settings

Table 20 below shows the default communication settings when Modbus

is enabled at the factory.

Table 20

Default Communication Settings

Setting

Default Value Configuration mode command for changing

the value*

Bit rate

19200

SERI

Number of data bits

8

Parity

E

Number of stop bits

1

Device address

240

ADDR

Response delay

0

SDELAY

Communication mode

MODBUS

SMODE

* See Table 6 on page 36.

NOTE

You can also change device address with Modbus itself (register 1537).

Supported Modbus Functions

Table 21

Supported Function Codes

Function

Code

(decimal)

Function Code

(hexadecimal)

Function Name

(as defined by the specification)

Notes

3

03

Read Holding Registers

See Table 22 on page 67

for available registers.

16

10

Write Multiple Registers

See Table 22 on page 67

for writable registers.

43 14

2B 0E

Read Device Identification

See Table 23 on page 68

for available device

identification objects.

NOTE

After power-up, wait for five seconds before sending Modbus requests.