List of serial commands, Table 6 – Vaisala DPT146 User Manual
Page 38
User's Guide _______________________________________________________________________
36 ___________________________________________________________________ M211372EN-D
List of Serial Commands
All commands can be issued either in uppercase or lowercase. In the
command examples, the keyboard input by the user is in bold type.
The notation
your computer keyboard. Enter a
before starting to enter commands.
Table 6
List of Serial Commands
Command
Description
?
Show device information
??
Show device information (overrides poll mode)
ADDR [0 … 255]
Show or set transmitter address
AERR
Set analog output error level
AMODE
Set analog output mode
AOVER [ON/OFF]
Allow analog outputs to exceed their range 10%
ASEL
Set analog output parameters and scaling
ATEST
Test analog outputs
CLOSE
Close the temporary connection and return the
device to POLL mode
ERRS
Display the currently active errors
FORM [modifier string] Set output format
FRESTORE
Restore factory settings
HELP
Show list of currently available serial commands
INTV [0 ... 255 S/MIN/H] Set the continuous output interval (for RUN mode
and R command)
OPEN [0 … 255]
Open a line to transmitter at defined address
R
Start the continuous outputting
RESET
Reset the transmitter
S
Stop the continuous outputting
SDELAY [0 … 255]
Set response sending delay
SEND [0 … 255]
Output readings once (specify address for
transmitters in POLL mode)
SERI [baud p d s]
Show or set the serial interface settings
SMODE [mode]
Show or set startup serial mode:
RUN, STOP, POLL, or MODBUS
SNUM
Display transmitter serial number
TIME
Show transmitter uptime
UNIT [m/n]
Select metric or non-metric units
VERS
Show transmitter firmware version