beautypg.com

Table 10, Hms82/83 – Vaisala HMDW80 User Manual

Page 48

background image

User's Guide _______________________________________________________________________

46 ___________________________________________________________________ M211510EN-C

Table 10

Specifications for HMD82/83, TMD82/83, HMW88/89,

and HMS82/83

Property

Description / Value

Operating environment

Operating temperature range

-40 ...+60 °C (-40 ... +140 °F)

Operating humidity range

0 …100 %RH

Relative humidity

Measurement range

0 … 100 %RH

Accuracy

Temperature range

+10 ... +30 °C (+50 ... +86 °F)

0 ... 90 %RH

±3 %RH

90 … 100 %RH

±5 %RH

Temperature range

-20 ... +10 °C, +30 ... +60 °C

(-4 ... +50 °F, +86 ... +140 °F)

0 ... 90 %RH

±5 %RH

90 … 100 %RH

±7 %RH

Temperature range -40 … -20 °C

(-40 … -4 °F)

0 … 100 %RH

±7 %RH

Stability in typical HVAC applications

±2 %RH over 2 years

Humidity sensor

Vaisala INTERCAP

®

Temperature

Measurement range

-40 ...+60 °C (-40 ... +140 °F)

Accuracy

At +20 °C (+68 °F)

±0.3 °C (±0.54 °F)

Temperature dependence

±0.01 °C/°C

Temperature sensor

Pt1000 RTD Class F0.1 IEC 60751

Calculated parameters

Measurement range for dewpoint

temperature and wet bulb temperature -40 ...+60 °C (-40 ... +140 °F)

Measurement range for enthalpy

-40…460 kJ/kg (-10…+190 BTU/lb)