beautypg.com

Mtl-20-lcd specifications, Mtl-30-lcd specifications – Dwyer GDL-T User Manual

Page 33

background image

DwyerLog User’s Guide

Version 1.4x

33/33

MTL-20-LCD Specifications

Display

Displays real time temperature. Displays logging status and alarm status.

Sample Point Capacity

43,344 Temperature samples..

Sample Rate

1 second to 18 hours.

Alarms

Visual over and under temperature alarm indicator.

Operating Temperature

-4°F to 140°F (-20°C to 60°C)

Storage Temperature

-4°F to 160°F (-20°C to 70°C)

Temperature Accuracy

+/-1°F (0.5°C)

Temperature Resolution

0.1°F or 0.1°C

Calibration

Password protected single point offset calibration is available through software.

Time Accuracy

+/-100ppm @75°F

Dimensions

3’’ x 1.6" x 0.6’’ (7.6cm x 4.0cm x 1.5cm)

Weight

1.0 oz (28g)

Power Source

3V CR2032 Lithium coin cell battery (Included)

Battery Life

3 Years. The logger automatically turns itself OFF after 1 hour, when not logging.
Turn On by pressing the button.

MTL-30-LCD Specifications

Display

Displays real time temperature and relative humidity. Displays logging status and
alarm status.

Sample Point Capacity

43,344 points for temperature only. 21,672 points for temperature, humidity and
dew point.

Alarms

Visual over and under alarm indicator for temperature and humidity

Sample Rate

1 second to 18 hours.

Operating Temperature

-4°F to 140°F (-20°C to 60°C)

Storage Temperature

-4°F to 160°F (-20°C to 70°C)

Temperature Accuracy

+/-1°F (0.5°C)

Temperature Resolution

0.1°F or 0.1°C

Relative Humidity Range

0% to 99%RH, non condensing.

Relative Humidity
Accuracy

+/- 2%RH, from 10% to 90% RH

Relative Humidity
Resolution

0.1 %RH

Calibration

Password protected single point offset calibration is available through software for
temperature and relative humidity.

Time Accuracy

+/-100ppm @ 75°F

Dimensions

3’’ x 1.6" x 0.6’’ (7.6cm x 4.0cm x 1.5cm)

Weight

1.0 oz (28g)

Power Source

3V CR2032 Lithium coin cell battery (Included)

Battery Life

3 Years. The logger automatically turns itself OFF after 1 hour, when not logging.
Turn On by pressing the button.