Maintenance – Parts Replacement

30

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

990-2282A-001

How to remove and install battery locks (if available).

If your system is equipped with Battery

Locks, follow the below procedure to remove the battery locks.

Remove the M6 screw attaching the battery

lock to the shelf.

Push the battery lock to the left, push it

upwards and remove.

Use reverse procedures for installation of

battery locks.

Replacement.

Directions for replacement.

APC recommends that a whole battery module (four batteries) is replaced

at the same time to ensure optimal runtime (see Example 1). However, it is only necessary to replace two
batteries at the same time according to Example 2 and 3 in the below tables.

Caution

Batteries must be replaced by trained personnel only (see the section General safety
prior to Battery Module
replacement).

523mm/(20in)

Enclosure

Col A

Col B

Col C

Col D

Example 1

New

New

New

New

Example 2

New

New

Old

Old

Example 3

Old

Old

New

New

352mm/(14 in)

Enclosure

Col A

Col B

Example 1

New

New

New

New

Example 2

New

New

Old

Old

Example 3

Old

Old

New

New