Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

990-2282A-001

How to store the battery modules

The battery modules must be stored indoors and with their protective packaging still in place.

Stored batteries should be recharged at regular intervals depending on the storage temperature:

Caution:

Do not store the batteries for more than 12 months.

Replaceable parts (only trained personnel).

Ambient temperature:

-15° to 40°C/5°F to 104°F

Relative Humidity:

25-85% Non-condensing

Storage place free from vibration,

dust, direct sunlight, and moisture.

Storage Temperature

Recharge interval

-15° to 20°C/5°F to 68°F

9 months

20° to 30°C/68°F to 86°F

6 months

30° to 40°C/86°F to 104°F

3 months

Part

APC Part No.

Battery Module

SYBT4

Network Management Card with temperature sensor

AP9619

Note

APC recommends that a whole battery module (four batteries) is replaced at the same time to
ensure optimal runtime. However, it is only necessary to replace two batteries at the same
time. See section How to replace and install a battery module, Directions for replacement.