Operation – Operation Procedures

990-2282A-001

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

9

Parallel System – turning into external bypass.

P

Warning

In bypass operation the batteries are still charged. If a total power off is required, the batteries
must be pulled out to the red disconnect line, see the section How to perform a total power off.

From the UPS: Check that all UPS units are in

bypass on each of the displays.

From the external MBP: Check that the bypass

lamp indication is lit

(Q003)

.

From the external MBP: Turn the bypass

switch (

Q003

) to position “1”

(ON)

.

From the external MBP: Check that the lamp

indication of the output isolation breaker is lit

(Q004)

.

From the external MBP: Turn the output

isolation breaker (

Q004

) to position “0”

(OFF)

.

From the UPS: Turn

OFF

each UPS from the

display via Control

Turn Load off

Yes,

Turn Load off.

From the external MBP: Check that all output

lamps are lit

(Q002)

.

From the external MBP: Turn all output

switches (

Q002

) to position “0”

(OFF)

.

From the external MBP: Turn all input

switches (

Q001

) to position “0”

(OFF)

.

From the XR Enclosure(s) (if available): Set

the DC disconnect switch (if available) to

position

OFF

.

From the UPS: Disconnect the batteries by

pulling them out to the red disconnect line.

From the XR Enclosure(s) (if available):

Disconnect the batteries by pulling them out to

the red disconnect line.

For a total UPS shut down see the section How

to perform a total power off.

Chrg 100%
Load 000%
xxxVin 000Vout x0Hz
Runtime: 0hr 0m

Press

Control
Status
Setup

Logging
Display
Diags

Help

Use

Press

UPS into Bypass
Do Self Test
Simulate Power Fail
Start Runtime Cal

Use

Press

Confirm:
UPS into Bypass
NO, ABORT
YES, UPS into Bypass

Use

Press