Operation – Operation Procedures

10

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

990-2282A-001

How to turn into normal operation

Single System – turning into normal operation from internal bypass.

Single System – turning into normal operation from external bypass.

Caution

Never attempt to switch back the UPS into normal operation till you have verified that there
are no internal UPS faults.

Check that the UPS is in bypass. The green

(

LOAD ON

) and the yellow (

BYPASS

) LEDs are

lit.

Turn the mechanical bypass lever downwards

into a horizontal position to deactivate the

internal bypass operation.

Press

ESC

to return to the previous menus and

turn out of bypass from the display via

Control–UPS out of bypass–Yes, UPS out

of bypass.

Check that the UPS is in normal operation.

The yellow (

BYPASS

) LED turns off and the

green (

LOAD ON

) LED remains lit.

Caution

Never attempt to switch back the UPS into normal operation till you have verified that there
are no internal UPS faults.

From the external MBP: Turn the output

switch (

Q002

) to position “1”

(ON)

.

From the UPS: Check that the yellow

(

BYPASS

) LED is lit and the green (

LOAD

ON

) LED is lit.

From the external MBP: Turn the bypass

switch (

Q003

) to position “0”

(OFF)

.

From the UPS: Turn out of bypass from the

display via Control–UPS out of bypass–

Yes, UPS out of bypass.

From the UPS: Check that the UPS is in

normal operation. The yellow (

BYPASS

)

LED turns off and the green (

LOAD ON

) LED

remains lit.