Operation – Operation Procedures

8

Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation

990-2282A-001

Turn the internal mechanical bypass

lever upwards to activate it. The load

will now be supported directly by

utility/mains power.

Reinstall the Front Panel.

Single System – turning into external bypass.

Warning

In bypass operation the batteries are still powered. If a total power off is required the batteries
must be pulled out to the red disconnect line, see the section How to perform a total power off.

From the external MBP: Turn the bypass

switch

(Q003

) to position “1”

(ON)

.

From the external MBP: Turn the output

switch (

Q002

) to position “0”

(OFF)

.

If the UPS has to be completely isolated/

removed, see the section How to perform a

total power off.

Chrg 100%
Load 000%
xxxVin 000Vout x0Hz
Runtime: 0hr 0m

Press

Control
Status
Setup

Logging
Display
Diags

Help

Use

Press

UPS into Bypass
Do Self Test
Simulate Power Fail
Start Runtime Cal

Use

Press

Confirm:
UPS into Bypass
NO, ABORT
YES, UPS into Bypass

Use

Press