Specification, Specification 41 – Dwyer UFB User Manual
Page 45
7: Specification
41
7: Specification
GENERAL
DSP Measurement Technique:
Transit time.
Timing Resolution:
50 pico-second, continuous signal level indication on display.
Flow Velocity Range:
Minimum Velocity 0.33 ft/s; Max Velocity 33 ft/s: Bi-directional.
Turn Down Ratio:
200:1
Accuracy:
±0.5% to ±2% of flow reading for flow rates >0.03 ft/s and Pipe OD >3.0 in (75 mm).
±3% of flow reading for flow rates >0.03 ft/s and Pipe OD in range 0.5 to 3.0 in (13 to 75 mm).
±6% of flow reading for flow rates <0.03 ft/s.
Repeatability:
±0.5% of measured value or ±0.03 ft/s whichever is the greater.
Reynolds Number Correction:
Flow velocity corrected for Reynolds number over entire velocity range.
Response Time:
< 500 ms depending on pipe diameter.
Selectable Flow Units:
VELOCITY: m/sec, ft/sec.
VOLUME: L/s, L/min, L/h, gal/s gal/min, gal/h, USgals/s, USgals/min, USgals/h, Barrel/h, Barrel/
day, m³/s, m³/min, m³/h.
Selectable Volume Units:
US gallons, gallons, barrels (oil), liters, m³.
Total Volume:
12 Digits - forward and reverse.
APPLICABLE FLUID TYPES
Fluid Condition:
Clean liquids or oils that have less than 3% by volume of particulate content. Applications include
river water, sea water, potable water, demineralized water, glycol/water mix, hydraulic systems
and diesel oil.
APPLICABLE PIPE TYPES
Pipe Materials:
Any sonic conducting medium such as Carbon Steel, Stainless Steel, Copper, UPVC, PVDF,
Concrete, Galvanized Steel, Mild Steel, Glass, Brass. Including Lined Pipes - Epoxy, Rubber,
Steel, Plastic.
Pipe Dimension (outside diameter):
Min 0.5
inch (13 mm); Max 197 inches (5000 mm) with D sensor set.
Pipe Wall Thickness:
0.04 to 3.0 inches (1 to 75 mm).
Pipe Lining:
Applicable pipe linings include Rubber, Glass, Concrete, Epoxy, Steel.
Pipe Lining Thickness:
0.0 to 1.0 inches (0 to 25 mm).
Pipe Wall Temperature Range:
Standard sensor operating temperature is -4°F to +275°F (-20°C to +135°C).