beautypg.com

Advanced Protection XRL User Manual

Page 5

background image

5

and ensure that nearest breaker positions are used. If new

construction, adjust breaker locations as appropriate.

Tip: Voltage drops for normal 120V or 277V lines might be 2-3V

per hundred feet. In surge applications, voltage drops might

be 100-150V per foot. These voltage drops add to clamping

voltage, thus hurting performance. Make every effort to keep

leads short and straight.

As distribution gear becomes larger, shorter leads are more

difficult to accomplish. When longer leads are unavoidable,

gently twist leads together (one to two twists per foot), or

tie-wrap leads together.

Tip: surges create magnetic fields per the ‘right-hand rule’.

When current goes in direction of thumb, magnetic field is

in direction of curl of fingers. As surge current goes to SPD,

fields are created in one direction. When the SPD sends those

currents to neutral and/or ground, current goes in the opposite

direction. If ‘coming & going’ are on the same axis, the magnetic

fields can be cancelled, thus avoiding performance decrease.

Gentle twists, bundling & tie-wraps accomplish this.

Shortest Leads Possible

Leads must be as short and straight as possible -

See NEC

®

Art. 285.12

Pretend wire is $1000 per foot coming out of your pocket.

No long leads

No sharp bends

No wire nuts

How short is short enough? As short as you can make it.

How long is too long? If anyone else can make it shorter.

Overcurrent Protection

SPDs draw very little current under normal conditions and

conduct for a brief duration upon encountering a transient

surge current. This SPD contains internal overcurrent and

overtemperature protection to protect against abnormal

voltage conditions.

Supplemental overcurrent protection is not required to protect

this SPD. However, connecting conductors require protection

in Type 2 or 4 applications. Follow applicable codes.

Voltage Rating

Before installing SPD, verify that it has the same voltage

rating as the power distribution system. Compare the SPDs

nameplate voltage or model number and ensure that SPD

configuration matches the intended power source. See Table 1.

The specifier or the user of the device should be familiar with

the configuration and arrangement of the power distribution

system in which any SPD is to be installed. The system

configuration of any power distribution system is based strictly

on how the secondary windings of the transformer supplying

the service entrance main or load are configured. This includes

whether or not the transformer windings are referenced to

earth via a grounding conductor. The system configuration is

not based on how any specific load or equipment is connected

to a particular power distribution system.

480V System Example: SPDs should be installed per

the electrical system, not per a load or motor’s wiring

connection. For example, a 480V three phase motor might

appear to be connected as a 480V Delta. In actuality, the

serving distribution system might be a 480Y/277V grounded

Wye, with or without a neutral pulled to the motor or MCC.

The system is still a 480Y/277V Wye, even though the load

is connected as a Delta. A grounded Wye has a defined

reference to ground (i.e., neutral is bonded to ground).

Some Delta systems are ungrounded, which have no

reference to ground and are known to become unstable in

certain situations. Such instability can cause line to ground

voltage fluctuations that may prematurely fail SPDs. For this

reason, the NEC

®

Article 285 has placed SPD restrictions

on ungrounded systems. As generalizations, SPDs for

ungrounded systems can be installed on grounded systems

with a clamping performance penalty. However, SPDs for

grounded systems installed on ungrounded systems are

almost certainly destined for premature failure. Call APT

Tech Support at (800) 237-4567 for further information.

Circuit Breaker and Disconnect Switch

The XA & XB family SPDs are tested and qualified as a Type

1 SPD per UL 1449 Third Edition and 2008 NEC

®

. This SPD

can be installed on the line side of the service overcurrent

device per 2008 NEC

®

Article 285. As a generalization, it

is more practical to install on load side of main overcurrent

device for maintenance reasons.

When connected on load side of main disconnect, we suggest

connecting via a 60A circuit breaker. The circuit breaker is

the intended disconnect switch and provides short circuit

protection to the connecting conductors. These SPDs have

internal overload protection elements within the product. A

breaker or disconnect is not required for the SPDs overcurrent

protection. These SPDs have demonstrated 200kA Short

Circuit Current Ratings (SCCRs). 120V & 120/240V models

have demonstrated 100kA SCCRs. Refer to label on unit.

Terminals

Terminals will accept 14 - 2 AWG conductor and are provided

for line (phase), neutral (if used), and equipment safety ground

connections. 8 AWG is the minimum recommended wire size

because UL testing and evaluation was performed using 8 AWG.

Wire Size and Installation Torque

This is a parallel-connected SPD; it is not series-connected.

The size of the SPD wiring is independent of the ampere

rating of the protected circuit. Recommended wire is 6

AWG for phase, neutral and ground connections. Torque

connections to 18 inch-pounds. Conductor length should

be as short as possible.

If other wire sizes are used, we recommend that all

conductors be the same gauge. Note that larger conductor

might appear to be beneficial. However, large conductor

tends to have the same inductance as smaller conductor,

thus netting limited improvement in exchange for being more

difficult to work with. Terminals accept 14 - 2 AWG conductor

with 6 AWG being preferred. Coordinate conductor size and

overcurrent protection per applicable codes.

If equipped, Disconnect Switch will accept 6 AWG to 1/0

AWG, with 6 AWG preferred. Torque connections to 18

inch-pounds. Do Not overtorque connections on Disconnect

Switch as it Will Break the Disconnect Switch and will not

be covered by warranty.

System Grounding

An equipment grounding conductor must be used on all

electrical circuits connected to the SPD.

For the best performance, use a single point ground system

where the service entrance grounding electrode system is

connected to and bonded to all other available electrodes,

building steel, metal water pipes, driven rods, etc. (for

reference see: IEEE Std 142-2007).

This manual is related to the following products: