beautypg.com

Figure 8 nema 3r drain holes figure 9, Diagnostic display panel – Advanced Protection XRL User Manual

Page 10

background image

10

OPERATION

Diagnostic Display Panel

All indicators and controls are located on the diagnostic

panel. The diagnostic panel is located on the front of the SPD

enclosure or behind the door on certain optional enclosures.

Each phase features a Green LED indicator. Green LEDs

indicate correct operation.

If an inoperative condition were to occur, the built-in audible

alarm will sound and the red Service LED will illuminate.

This indicates that the unit needs evaluation by a qualified

electrician or technician. Until a qualified person evaluates

the unit, press Alarm Silence to silence the alarm. (The

LED above Alarm Silence illuminates when the alarm

is deactivated. Normal operation occurs with the Alarm

Silence LED extinguished.) The red Service LED will

remain illuminated even though the Audible Alarm has been

silenced. Test tests the red Service LED, the Audible Alarm,

and changes the state of Dry Contacts (if equipped).

If LEDs are illuminated in a manner that suggests

contradictory information, there may be an internal logic

problem and the unit needs replaced. If none of the LEDs

are illuminated, the unit may not be installed correctly. For

troubleshooting assistance, please contact APT Technical

Support at (800) 237-4567.

Surge Counter Option

The surge counter registers the number of transient

overvoltages on all L-N and L-G modes since the counter

was last reset. The counter is inductively coupled from each

mode of protection. It increments upon significant current

change in a short time period (large di/dt).

The surge counter includes Count and Reset buttons on

the touchpad display. Pressing Count adds one count.

Pressing Reset clears the counter’s memory and sets the

display to zero.

The counter includes an Eprom memory chip to store the

surge count in the event of a power loss. The Eprom requires

no maintenance giving it an advantage over replaceable

batteries. The surge counter display will be blank if all power

is lost to the SPD but will retain the last count shown on the

display once power is returned.

NEMA 3R Drain Holes for Standard Steel Enclosure

In order to maintain a UL 3R rating, two 0.25” (6mm) holes

must be drilled in opposite corners of the bottom surface

of the enclosure. Take care to not damage internal SPD

components. Remove any drilling remnants. (Do not perform

on other enclosures or ratings.)

Figure 8

NEMA 3R DRAIN HOLES

Figure 9

Phase A, B & C: Green LED indicators—one per

phase. Green is good. Out indicates problem. Every

suppression element in this SPD is monitored. (N-G

indicates on Phase A)

Service LED (Red): LED illuminates in the event

of problems. This indicator is logic-connected to the

Phase LEDs. Should a Phase LED go out the Service

LED will illuminate and the Audible Alarm will sound.

Test: Tests red Service LED and Audible Alarm, and

changes state of Dry Contacts.

Alarm Silence: Turns Audible Alarm off. (Alarm is

deactivated when the Silence LED is illuminated.)

Surge Counter Count: (if equipped) Increments

optional surge counter by one. (+1)

Surge Counter Reset: (if equipped) Resets optional

surge counter to zero. (0)

DIAGNOSTIC DISPLAY PANEL

Phase B

Phase C

Service

Phase A

Advanced Protection Technologies

Test

Count

Reset

Silence

Surge Counter

Phase C

Service

Phase B

Phase A

Surge Counter

Advanced Protection Technologies

Silence

Test

Count

Reset

This manual is related to the following products: