beautypg.com

Advanced Protection SPDee DC User Manual

Installation, operation & maintenance manual, Warning, Dc voltage surge protective device

background image

SPD

EE

DC Voltage Surge Protective Device

DC

Installation, Operation

& Maintenance Manual

(800) 237-4567

·

(727) 535-6339

·

Fax (727) 539-8955

Advanced Protection Technologies

www.aptsurge.com

·

[email protected]

14550 58th Street North

·

Clearwater, Florida 33760

UL is a registered trademark of Underwriters Laboratories, NEC

®

and National Electrical Code are

registered trademarks of National Fire Protection Association, C62.41.1-2002, C62.41.2-2002,

C62.45-2002, C62.72-2007 are registered trademarks of IEEE.

10.9.12.lh #8379

European Authorized Representative

Obelis s.a.

Boulevard Général Wahis 53

1030 Brussels, BELGIUM

Tel: +(32) 2. 732.59.54

Fax: +(32) 2. 732.60.03

E-Mail: [email protected]

DC Voltage Photovoltaic System Instructions – Do Not Use for AC Voltage Installation

Save These Instructions - This manual contains important instructions that shall be followed

during installation and maintenance of the power system.

Presently, there is no dedicated UL standard

for higher voltage DC SPDs. The following

SPD

ee

s comply with most recent regulatory

actions including UL 1449 Third Edition

Listing (VZCA.E321351) and compliance to

the UL Certification Requirement Decision

(CRD) regarding DC rated SPDs for

Photovoltaic Systems. UL 1449 certification

requires AC voltage specific language,

which is also included below.

Thank you for choosing an APT SPD

ee

Surge Protective Device (SPD). SPD

ee

is a high quality, high

energy surge suppressor designed to protect sensitive equipment from damaging transient overvoltages.

SPD

ee

is parallel connected such that circuit ampacity is unlimited. Proper installation is important to

maximize performance. Please follow steps outlined herein. These instructions are not intended to replace

national or local codes. Follow all applicable electrical codes to ensure compliance.

UL 1449 Third Edition (Sept 2009), 2008 NEC

®

Article 285 and CSA C22.1 (CEC) generated substantial

changes regarding AC voltage SPDs.

Be aware that photovoltaic systems generate maximum

voltage at coldest temperatures and brightest light. For

example, full sunup after a cool/cold night produces

maximum voltage on photovoltaic systems. The system’s

maximum voltage rating should take this into account.

The following graphic on the SPD’s label represents DC

voltage:

ENGLISH

Read this manual in entirety prior to installing

Only qualified licensed electricians should install or service SPDs

SPDs should never be installed or serviced when energized or during electrical storms

Use appropriate safety precautions including Personal Protection Equipment

Failure to follow these instructions can result in death, serious injury, and/or

equipment damage

When used in outdoor applications, customer must seal the conduit nipple using

watertight fittings (not included) to ensure a watertight connection

WARNING

– Risk of Electric Shock

TABLE 1:

Range of Input

Operating Voltage

Maximum Input

Voltage

S50A300VDC

0 – 375V DC

424V DC

S50A600VDC

0 – 750V DC

905V DC

S50A1000VDC

0 – 1000V DC

1188V DC