NEC

®

Article 285 & UL 1449-3

SPD Types: Types 1, 2, 3, & 4

Based on Location within electrical distribution system

(also coincides with ANSI/IEEE C62.41.2 - 2002 Categories C, B &A)

Only qualified licensed electricians should install or service SPDs

SPDs should never be installed or serviced when energized or during electrical storms

Use appropriate safety precautions including Personal Protection Equipment

Failure to follow these instructions can result in death, serious injury, and/or

equipment damage

When used in outdoor applications, customer must seal the conduit nipple using

watertight fittings (not included) to ensure a watertight connection

Read this manual in its entirety prior to installing

WARNING

– Risk of Electric Shock

Installation, Operation

& Maintenance Manual

(800) 237-4567

·

(727) 535-6339

·

Fax (727) 539-8955

Advanced Protection Technologies

www.aptsurge.com

·

[email protected]

14550 58th Street North

·

Clearwater, Florida 33760

UL is a registered trademark of Underwriters Laboratories, NEC

®

and National Electrical Code are

registered trademarks of National Fire Protection Association, C62.41.1-2002, C62.41.2-2002,

C62.45-2002, C62.72-2007 are registered trademarks of IEEE.

7.9.13.lh #8078

European Authorized Representative

Obelis s.a.

Boulevard Général Wahis 53

1030 Brussels, BELGIUM

Tel: +(32) 2. 732.59.54

Fax: +(32) 2. 732.60.03

E-Mail: [email protected]

ENGLISH

Thank you for choosing an APT XCS Surge Protective Device (SPD). The XCS is a high quality, high

energy surge suppressor designed to protect sensitive equipment from damaging transient overvoltages.

The XCS is parallel connected such that circuit ampacity is unlimited. Proper installation is important to

maximize performance. Please follow steps outlined herein. These instructions are not intended to replace

national or local codes. Follow all applicable electrical codes to ensure compliance.

UL 1449 Third Edition (Sept 2009) and 2008

NEC

®

Article 285 generated substantial

changes regarding SPDs.

The XCS complies with latest regulatory

actions and is UL 1449 Listed as such

(VZCA.E321351). There is new emphasis on

installation location, identified as Types 1, 2,

3 and 4, outlined below.

SPD Types (see 2008 NEC

®

Article 285 and/or UL 1449-3):

Type 1: Installation on the line side or load side of the service

disconnect overcurrent device and may be used in Type 2 or Type

4 installations. Examples: surge arrestors, lightning arrestors,

meter hubs, metering cabinets, ran out of breaker positions, etc..

Type 2: Downstream of service disconnect; probably will

connect via breaker. Examples: switchboards, power panels,

panelboards, equipment, motors, pumps, etc.

Type 3: Plug-in SPD

Type 4: Usually treated as a UL Recognized component in a larger

UL Listed finished product. Examples: UL 508 control panels, medical

equipment, wind turbines, signage, conveyers, elevators, etc.

TE

XCS

Series

Surge Protective Device (SPD)