4 Configuration parameters

76

4.2.11Configuration - Undocumented parameters

4.2.12Configuration - Fine calibration

Parameter

Value/Selection

Description

Undocumented
parameter 1 — 40

Configuration
➔ Undoc. parameter

➔ Par. 1 — 40

These parameters are
intended for customer-
specific adaptation.
Alteration to the settings
may only be carried on the
express instruction of the
equipment manufacturer.

Parameter

Value/Selection

Description

Calibration status

Configuration
➔ Fine calibration

➔ Analog input 1 — 6

➔ Calibration status

Off,
On

A calibration (adjustment)
of the analog
measurements can be
activated here. The
adjustment is carried out
using a linear equation.

Actual start value

Configuration
➔ Fine calibration

➔ Analog input 1 — 6

➔ Actual start value

-99999 to 0 to +99999

Start value for
actual line.
Only active when
calibration status = On.

Set start value

Configuration
➔ Fine calibration

➔ Analog input 1 — 6

➔ Set start value

-99999 to 0 to +99999

Start value for
target line.
Only active when
calibration status = On.

Actual end value

Configuration
➔ Fine calibration

➔ Analog input 1 — 6

➔ Actual end value

-99999 to 1000 to +99999

End value for
actual line.
Only active when
calibration status = On.

Set end value

Configuration
➔ Fine calibration

➔ Analog input 1 — 6

➔ Set end value

-99999 to 1000 to +99999

End value for
target line.
Only active when
calibration status = On.

H

Systematic errors, such as those caused by an unsuitable probe
mounting, for example, can be compensated through fine
calibration.

Example:

A sensor covers temperatures from 200 to 300°C.
It is built into a tunnel oven so unfavorably that it always indicates
10°C less than the temperature of the oven contents. The incorrect
measurement can be corrected through fine calibration.

Actual start value

: 200°C

Set start value

: 210°C

Actual end value

: 300°C

Set end value

: 310°C