OUTPUTS

RELAY OUTPUTS OUT1, OUT2

Contact type:

2 NO contacts with
common connection

Max. contact rating:

500 VA, 250 V, 2A at
48...62 Hz,
resistive load

Min. contact rating:

6V, 1 mA DC

Operating life (electr.):

800.000 duty cycles with
max. rating

RELAY OUTPUT OUT3

Contact type:

potential-free changeover
contact

Max.contact rating:

500 VA, 250 V, 2A at 48...62
Hz,
resistive load

Min. contact rating:

5V, 10 mA AC/DC

Operating life (electr.): 600.000 duty cycles with

max. contact rating

Note:
If the relays OUT1...OUT3 operate external
contactors, these must be fitted with RC
snubber circuits to manufacturer specifications
to prevent excessive switch-off voltage peaks.

POWER SUPPLY

AC SUPPLY

Voltage:

90...250 V AC

Frequency:

48...62 Hz

Power consumption

approx. 7,3 VA

BEHAVIOUR WITH POWER FAILURE

Configuration, parameters and adjusted
set-points, control mode:
Non-volatile storage in EEPROM

ENVIRONMENTAL CONDITIONS

Protection modes

Front panel:

IP 65 (NEMA 4X)

Housing:

IP 20

Terminals:

IP 00

Permissible temperatures

For specified
accuracy:

0...60°C

Warm-up time:

≥ 15 minutes

For operation:

-20...65°C

For storage:

-40...70°C

Humidity

75% yearly average, no condensation

Altitude

To 2000 m above sea level

Shock and vibration

Vibration test Fc (DIN 68-2-6)

Frequency:

10...150 Hz

Unit in operation:

1g or 0,075 mm

Unit not in operation: 2g or 0,15 mm

Shock test Ea (DIN IEC 68-2-27)

Shock:

15g

Duration:

11ms

Electromagnetic compatibility

Complies with EN 61 326-1
(for continuous, non-attended operation)

33

KS40-1 burner