Signaller with switch-over contact 15, Con1 – West Control Solutions KS 40-1 Burner User Manual
Page 15
After exit from the configuration level (see page 43, the controller is re-initiali-
zed (all display elements are lit) and changes over to normal operation (operating
level).
g
Leading zeros are not displayed (ex.: display 400 with code
0400)
Configuration example 1 (code 0400):
KS40-1 as a signaller with
switch-over contact for 2-stage burner:
Measuring range 0...200°C,
Resistance thermometer Pt 100,
Reaction at sensor break
as process value higher than set-point.
Configuration example 2 (code 2120):
KS40-1 as 3-point stepping controller:
Connection to pressure transmitter P30/W,
Measuring range 0,00...1,00 bar,
Reaction at sensor break as process value
smaller than set-point.
Function: Signaller with switch-over contact
CAUTION: The two relays
1 and 2 are coupled, i.e.
the contacts have
switch-over function. En-
sure that the two relays are
not energized or de-energi-
zed simultaneously. Ex-
ception: de-energized
condition.
Settings:
Switching differences:
Sd1: in physical values
Limit value
OUT3:
The relay is de-energized when exceeding the limit.
Upper limit value
H.1 : in units of phys. quantity.
Switching difference
HYS.1 : in units of phys.quantity
Signalling LEDs:
LED1:
lit when
OUT1 is energized
LED2:
lit when
OUT2 is energized
LED3:
lit when
OUT3 is energized
OK-LED: lit, unless the limit value is reached
Parameter:
see chapter 5 “Parameter level”
Configuration level
Configuration with
qUIC
15
KS40-1 burner
123.8
400
123.8
Con1
123.8
2120
123.8
Con1
HYS.1
Limit
OUT3
OUT2
-X
W
X
W
W
Sd1
Sd2
=
OUT1
ON
ON
OFF
OFF
ON
H.1
OFF