Inp.2, Configuration level – West Control Solutions KS 40-1 Burner User Manual
Page 20
Configuration level
KS40-1 burner
20
InP.2
Name
Value range
Description
Default
Own
setting
I.Fnc
Function selection of INP2
0
0
No function
2
External set-point
SP.E (switching -> LOGI/ SP.E)
S.tYP
Sensor type selection
30
20
Pt100 (-200,0 ... 100,0 °C)
21
Pt100 (-200,0 ... 850,0 °C)
22
Pt1000 (-200,0...200,0 °C)
30
0...20mA / 4...20mA 1
50
Potentiometer ( 0...160 Ohm) 1
51
Potentiometer ( 0...450 Ohm) 1
52
Potentiometer ( 0...1600 Ohm) 1
Corr
Measured value correction / scaling
0
0
Without scaling
1
Offset correction (at
CALlevel)
2
2-point correction (at
CALlevel)
3
Scaling (at
PArA level)
1 With current or potentiometer input signals, scaling is required (see section 5.1).
Lim
Name
Value range
Description
Default
Own
setting
Fnc.1
Fnc.2
Fnc.3
Function of limit 1 / 2 / 3
1 / 0 / 0
0
Switched off
1
Measured value monitoring
2
Measured value monitoring + alarm status storage. A stored
limit value can be reset via error list, Ò-key or a digital input (
->
LOGI/ Err.r)
Src.1
Src.2
Src.3
Source of limit 1 / 2 / 3
1 / 0 / 0
0
Process value = absolut alarm
1
Control deviation Xw (process value - set-point) relativ alarm
2
Control deviation Xw (relativ alarm) with suppression after
start-up and set-point change
6
Effective set-point Weff
7
Correcting variable (controller output)
LP.AL
Monitoríng of control loop interruption
0
0
Switched off
1
LOOP alarm active