Configuration level

KS40-1 burner

20

InP.2

Name

Value range

Description

Default

Own

setting

I.Fnc

Function selection of INP2

0

0

No function

2

External set-point

SP.E (switching -> LOGI/ SP.E)

S.tYP

Sensor type selection

30

20

Pt100 (-200,0 ... 100,0 °C)

21

Pt100 (-200,0 ... 850,0 °C)

22

Pt1000 (-200,0...200,0 °C)

30

0...20mA / 4...20mA 1

50

Potentiometer ( 0...160 Ohm) 1

51

Potentiometer ( 0...450 Ohm) 1

52

Potentiometer ( 0...1600 Ohm) 1

Corr

Measured value correction / scaling

0

0

Without scaling

1

Offset correction (at

CALlevel)

2

2-point correction (at

CALlevel)

3

Scaling (at

PArA level)

1 With current or potentiometer input signals, scaling is required (see section 5.1).

Lim

Name

Value range

Description

Default

Own

setting

Fnc.1
Fnc.2
Fnc.3

Function of limit 1 / 2 / 3

1 / 0 / 0

0

Switched off

1

Measured value monitoring

2

Measured value monitoring + alarm status storage. A stored

limit value can be reset via error list, Ò-key or a digital input (

->

LOGI/ Err.r)

Src.1
Src.2
Src.3

Source of limit 1 / 2 / 3

1 / 0 / 0

0

Process value = absolut alarm

1

Control deviation Xw (process value - set-point) relativ alarm

2

Control deviation Xw (relativ alarm) with suppression after

start-up and set-point change

6

Effective set-point Weff

7

Correcting variable (controller output)

LP.AL

Monitoríng of control loop interruption

0

0

Switched off

1

LOOP alarm active