Out.1 / 2 / 3, Logi, Configuration level – West Control Solutions KS 40-1 Burner User Manual
Page 21
Configuration level
21
KS40-1 burner
Out.1 / 2 / 3
Name
Value range
Description
Default
Own
setting
O.Act
Method of operation of output OUT1
Out.1: 0
Out.2: 0
Out.3: 1
0
Direct / normally open
1
Inverse / normaly closed
Y.1
Y.2
Controller output Y1 / Y2
Out.1: 1 / 0
Out.2: 0 / 1
Out.3: 0 / 0
0
Not active
1
Active
Lim.1
Lim.2
Lim.3
Limit 1 / 2 / 3 signal
Out.1: 0 / 0 / 0
Out.2: 0 / 0 / 0
Out.3: 1 / 0 / 0
0
Not active
1
Active
LP.AL
Interruption alarm signal (LOOP)
Out.1: 0
Out.2: 0
Out.3: 0
0
Not active
1
Active
FAi.1
FAi.2
INP1 / INP2 error signal
Out.1: 0 / 0
Out.2: 0 / 0
Out.3: 1 / 0
0
Not active
1
Active
LOGI
Name
Value range
Description
Default
Own
setting
L_r
Local / Remote switching (Remote: adjusting of all values by
front keys is blocked)
0
0
No function
1
Always active
3
DI2 switches *
4
DI3 switches *
5
è key switches *
SP.2
Switching to second set-point SP.2
3
0
No function
3
DI2 switches *
4
DI3 switches *
5
è key switches *
SP.E
Switching to external set-point SP.E
0
0
No function
1
Always active
3
DI2 switches *
4
DI3 switches *
5
è key switches *
Y2
Y/Y2 switching
0
0
No function
3
DI2 switches *
4
DI3 switches *
5
è key switches *
6
Ò key switches *