Out.1 / 2 / 3, Logi, Configuration level – West Control Solutions KS 40-1 Burner User Manual

Page 21

background image

Configuration level

21

KS40-1 burner

Out.1 / 2 / 3

Name

Value range

Description

Default

Own

setting

O.Act

Method of operation of output OUT1

Out.1: 0

Out.2: 0

Out.3: 1

0

Direct / normally open

1

Inverse / normaly closed

Y.1
Y.2

Controller output Y1 / Y2

Out.1: 1 / 0

Out.2: 0 / 1

Out.3: 0 / 0

0

Not active

1

Active

Lim.1
Lim.2
Lim.3

Limit 1 / 2 / 3 signal

Out.1: 0 / 0 / 0

Out.2: 0 / 0 / 0

Out.3: 1 / 0 / 0

0

Not active

1

Active

LP.AL

Interruption alarm signal (LOOP)

Out.1: 0

Out.2: 0

Out.3: 0

0

Not active

1

Active

FAi.1
FAi.2

INP1 / INP2 error signal

Out.1: 0 / 0

Out.2: 0 / 0

Out.3: 1 / 0

0

Not active

1

Active

LOGI

Name

Value range

Description

Default

Own

setting

L_r

Local / Remote switching (Remote: adjusting of all values by

front keys is blocked)

0

0

No function

1

Always active

3

DI2 switches *

4

DI3 switches *

5

è key switches *

SP.2

Switching to second set-point SP.2

3

0

No function

3

DI2 switches *

4

DI3 switches *

5

è key switches *

SP.E

Switching to external set-point SP.E

0

0

No function

1

Always active

3

DI2 switches *

4

DI3 switches *

5

è key switches *

Y2

Y/Y2 switching

0

0

No function

3

DI2 switches *

4

DI3 switches *

5

è key switches *

6

Ò key switches *