8 technical data 32, Technical data 32, Current signal measuring range 32 – West Control Solutions KS 40-1 Burner User Manual
Page 32: Resistance thermometer measuring range 32, Thermocouple measuring range 32, Voltage signal measuring range 32, 8technical data
8
Technical data
INPUTS
PROCESS VALUE INPUT INP1
Resolution:
> 14 bits
Decimal point:
0 to 3 digits behind the
decimal point
Dig. input filter:
adjustable 0,000...9999 s
Scanning cycle:
100 ms
Measured value
correction:
2-point or offset correction
Thermocouples
r Table 2 (page 58 )
Input resistance:
³ 1 MW
Effect of source resistance:
1
mV/W
Cold-junction compensation
Maximal additional error:
± 0,5 K
Sensor break monitoring
Sensor current:
£ 1 mA
Configurable output action
Resistance thermometer
r
Table 2 (page 58 )
Connection:
2 or 3-wire
Lead resistance:
max. 30 Ohm
Input circuit monitor:
break and short circuit
Potentiometric transducer 50-30-50
W
Current and voltage signals
r
Table 3 (page 58 )
Span start, end of span: anywhere within measuring
range
Scaling:
selectable -1999...9999
Linearization:
16 segments, adaptable
with BlueControl
Decimal point:
adjustable
Input circuit monitor:
12,5% below span start
(2mA, 1V)
SUPPLEMENTARY INPUT INP2
Resolution:
> 14 bits
Scanning cycle:
100 ms
Accuracy:
< 0,5 %
Current measuring range
Technical data as for INP1
Potentiometer
r
Table 2 (page 58 )
Connection:
3-wire
Lead resistance:
max. 30 Ohm
Input circuit monitor:
break
CONTROL INPUT DI2/DI3
Configurable as switch or push-button!
Connection of a potential-free contact suitable
for switching “dry” circuits.
Switched voltage:
5 V
Current:
160
mA
TRANSMITTER SUPPLY U
T
(OPTION)
Power:
22 mA /
³ 18 V
GALVANIC ISOLATION
Safety isolation
Function isolation
KS40-1 burner
32
Power supply
connections
Process value input INP1
Supplementary input INP2
Digital inputs di2, 3
Transmitter supply U
T
Relay outputs OUT 1,2
Relay output OUT3