background image

4

Configuration level

4.1 Configuration with

qUIC

At configuration level, the controller function is determined by changing configu-
ration word

Con1 . Con1 and the code adjusted for Con1 are displayed al-

ternately on the lower display line.

Code signification:

Configuration level

KS40-1 burner

14

Configuration with

qUIC

125

126

SP.X

SG

Err

Ada

r

М

И

М

Щ

3 sec.

r

PArA

ConF

r Ù r

qUIC

Ù

r

Con1

r

r Ù

r

123.8

1520

A B C D

123.8

Con1

A

0

Reaction at sensor break as process value higher than set-point.

1

Reaction at sensor break as process value smaller than set-point

2

Only P30/W connection, always process value smaller than set-point *

B

0

Potentiometric transducer 50-30-50 [ / pressure sensor 0..10V, display range

0,0...100,0 (%)

1

Potentiometric transducer 50-30-50 [ / pressure sensor 0..10V, display range

0,00...1,00 (bar)

2

Potentiometric transducer 50-30-50 [ / pressure sensor 0..10V, display range

0,0...16,0 (bar)

3

Potentiometric transducer 50-30-50 [ / pressure sensor 0..10V, display range

0,0...40,0 (bar)

4

Resistance thermometer Pt 100 [ , range 0...200°C

5

Resistance thermometer Pt 100 [ , range 0...400°C

6

Thermocouple type L, range 0...900°C

7

Thermocouple type K, range 0...1350°C

C

0

Signaller with switching

1

3-point signaller

2

3-point stepping controller (DPS) switchable to signaller (SG)

3

3-point stepping controller (DPS) switchable to 3-point signaller (SG)

D

0

Not changeable

* Only possible with A =

2 and B = 0 … 3