4 configuration level 14, 1 configuration with quic 14, Configuration with quic 14 - 17 – West Control Solutions KS 40-1 Burner User Manual
Page 14: Quic codes 14, Con1, R ù r, Rr ù r, 4configuration level 4.1 configuration with quic
4
Configuration level
4.1 Configuration with
qUIC
At configuration level, the controller function is determined by changing configu-
ration word
Con1 . Con1 and the code adjusted for Con1 are displayed al-
ternately on the lower display line.
Code signification:
Configuration level
KS40-1 burner
14
Configuration with
qUIC
125
126
SP.X
SG
Err
Ada
r
М
И
М
Щ
3 sec.
r
PArA
ConF
r Ù r
qUIC
Ù
r
Con1
r
r Ù
r
123.8
1520
A B C D
123.8
Con1
A
0
Reaction at sensor break as process value higher than set-point.
1
Reaction at sensor break as process value smaller than set-point
2
Only P30/W connection, always process value smaller than set-point *
B
0
Potentiometric transducer 50-30-50 [ / pressure sensor 0..10V, display range
0,0...100,0 (%)
1
Potentiometric transducer 50-30-50 [ / pressure sensor 0..10V, display range
0,00...1,00 (bar)
2
Potentiometric transducer 50-30-50 [ / pressure sensor 0..10V, display range
0,0...16,0 (bar)
3
Potentiometric transducer 50-30-50 [ / pressure sensor 0..10V, display range
0,0...40,0 (bar)
4
Resistance thermometer Pt 100 [ , range 0...200°C
5
Resistance thermometer Pt 100 [ , range 0...400°C
6
Thermocouple type L, range 0...900°C
7
Thermocouple type K, range 0...1350°C
C
0
Signaller with switching
1
3-point signaller
2
3-point stepping controller (DPS) switchable to signaller (SG)
3
3-point stepping controller (DPS) switchable to 3-point signaller (SG)
D
0
Not changeable
* Only possible with A =
2 and B = 0 … 3