5 parameter setting level 24, Cntr, Setp – West Control Solutions KS 40-1 Burner User Manual
Page 24: 5parameter setting level, Parameter setting level
5
Parameter setting level
Parameter setting level
KS40-1 burner
24
Cntr
Visible
with qUIC
Name Value range
Description
Default
Own
setting
f
Pb1
1...9999
Proportional band 1 (heating) in phys.
dimensions (e.g. °C)
10
Pb2
1...9999
Proportional band 2 (cooling) in phys.
dimensions (e.g. °C)
10
f
ti1
1...9999
Integral action time 1 (heating) [s]
10
ti2
1...9999
Integral action time 2 (cooling) [s]
10
f
td1
1...9999
Derivative action time 1 (heating) [s]
10
td2
1...9999
Derivative action time 2 (cooling) [s]
10
t1
0,4...9999
Minimal cycle duration 1 (heating) [s]. The
minimum impulse is 1/4 x t1
10
t2
0,4...9999
Minimal cycle duration 2 (heating) [s]. The
minimum impulse is 1/4 x t2
10
f
SH
0...9999
Dead zone or switching differential for
on-off control [phys. dimensions)
1
f
Sd1
0,0...9999
Switching differntial relais 1 for signaller
with partial/full load switch-over
0,1
f
Sd2
0,0...9999
Switching differntial relais 2 for 3-point
signaller
0,1
f
d.SP
-1999...999
9
Trigger point speration for series contact
D
/ Y / Off [phys. dimensions]
0
f
tP
0,1...9999
Minimum impulse [s]
OFF
f
tt
3...9999
Actuator response time for servo-motor [s]
60
Y.Lo
-120...120
Lower output limit [%]
0
Y.Hi
-120...120
Upper output limit [%]
100
Y2
-120...120
2. correcting variable
0
Y.0
-120...120
Working point for the correcting variable
[%]
0
Ym.H
-120...120
Limitation of the mean value Ym [%]
5
L.Ym
0...9999
Max. deviation xw at the start of mean
value calculation [phys. dimensions]
8
SETP
Visible
with qUIC
Name
Value range
Description
Default Own setting
SP.LO
-1999...9999
Set-point limit low for Weff
0
SP.Hi
-1999...9999
Set-point limit high for Weff
100
f
SP.2
-1999...9999
Set-point 2.
20
r.SP
0...9999
Set-point gradient [/min]
OFF