5.1 Input scaling (only visible with
qUIC = OFF)
When using current or voltage signals as input variables for
InP.1 or InP.2,
scaling of input and display values at parameter setting level is required. Specifi-
cation of the input value for lower and higher scaling point is in the relevant elec-
trical unit (mA/ V).
5.1.1 Input
Inp.1
g
Parameters
InL.1 , OuL.1, InH.1 and OuH.1 are only visible if
ConF / InP.1 / Corr = 3 is chosen.
In addition to these settings,
InL.1 and InH.1 can be adjusted in the range
(0...20mA / 0...10V) determined by selection of
S.tYP .
a
For using the predetermined scaling with thermocouple and resistance
thermometer (Pt100), the settings for
InL.1 and OuL.1 and for InH.1 and
OuH.1 must have the same value.
g
Input scaling changes at calibration level (r page 27) are displayed by input
scaling at parameter setting level. After calibration reset (
OFF), the scaling
parameters are reset to default.
5.1.2 Input
InP.2
As input
InP.1, but only S.Typ = 30 adjustable!
Parameter setting level
KS40-1 burner
26
Input scaling (only visible with
qUIC = OFF)
S.tYP
Input signal
InL.1
OuL.1
InH.1
OuH.1
30
(0...20mA)
0 … 20 mA
0
any
20
any
4 … 20 mA
4
any
20
any
40
(0...10V)
0 … 10 V
0
any
10
any
2 … 10 V
2
any
10
any
mA/V
phys.
quantity
mA / V
phys. quantity
OuH.x
OuL.x
InH.x
InL.x